CIRCUIT BREAKER FAIL PROTECTION
When a fault occurs, one or more protection devices will operate and issue a trip command to the relevant
circuit breakers. Operation of the circuit breaker is essential to isolate the fault and prevent, or at least limit,
damage to the power system. For transmission and sub-transmission systems, slow fault clearance can also
threaten system stability.
For these reasons, it is common practise to install Circuit Breaker Failure protection (CBF). CBF protection
monitors the circuit breaker and establishes whether it has opened within a reasonable time. If the fault
current has not been interrupted following a set time delay from circuit breaker trip initiation, the CBF
protection will operate, whereby the upstream circuit breakers are back-tripped to ensure that the fault is
isolated.
CBF operation can also reset all start output contacts, ensuring that any blocks asserted on upstream
protection are removed.
4.1
CIRCUIT BREAKER FAIL IMPLEMENTATION
Circuit Breaker Failure Protection is implemented in the
CB FAIL & I<
column of the relevant settings group.
Circuit breaker failure protection (CBF) uses logic to combine internally and externally generated trip signals
with current measurements and timers. Following a fault, if a circuit breaker has not operated, signals to
isolate the fault and the faulty circuit breaker are asserted.
By default, CBF is enabled. If you don’t want to use it,in the
CONFIGURATION
column set
CB Fail
to
Disabled
.
If CBF is set to
Enabled
and a fault occurs, the CBF sequence is initiated.
CBF is configured using a combination of:
●
settings contained in the CB FAIL column of the relevant settings group
●
mapping signals in the Programmable Scheme Logic (PSL).
Use
CBF Control By
to set the CBF reset condition. You can choose to reset if the
I< Current Set
threshold
is satisfied, you can choose to reset if a 52a contact indicates that the circuit breaker has operated correctly,
or you can use a combination of both.
The undercurrent reset element operates in less than one cycle.
The CBF has four timers. Two are used for a CBF that is initiated by internal protection. These are CB Fail 1
Timer (tBF1) and CB Fail 2 Timer (tBF2). The other two are used for a CBF that is initiated by external
protection. These are CB Fail 3 Timer (tBF3) and CB Fail 4 Timer (tBF4).
There is an overcurrent element that can be enabled to provide an additional input to the CBF logic.
The settings are common to all terminals in the scheme but the CBF logic is applied individually at each
terminal according to the specific terminal conditions.
Tripping for CBF conditions tries to minimise disruption to the system by monitoring the topology and
adapting the tripping decision to changing configurations.
4.2
CIRCUIT BREAKER FAIL LOGIC
The following diagram shows CBF logic for internally indicated faults. The digital input and output signals
(DDBs) that need mapping in the PSL are:
●
Int CBF Init Tn (n=1-18)
●
CBF Retrip Tn (n=1-18)
●
CBF Bktrip Zn (n=1-4)
MiCOM P747
Chapter 5 - Protection Functions
P747-TM-EN-1
111
P747-TM-EN-1.1
Summary of Contents for MiCOM P747 Agile
Page 2: ......
Page 16: ...Contents MiCOM P747 xiv P747 TM EN 1 P747 TM EN 1 1...
Page 20: ...Table of Figures MiCOM P747 xviii P747 TM EN 1 P747 TM EN 1 1...
Page 21: ...INTRODUCTION CHAPTER 1...
Page 22: ...Chapter 1 Introduction MiCOM P747 2 P747 TM EN 1 P747 TM EN 1 1...
Page 31: ...SAFETY INFORMATION CHAPTER 2...
Page 32: ...Chapter 2 Safety Information MiCOM P747 12 P747 TM EN 1 P747 TM EN 1 1...
Page 42: ...Chapter 2 Safety Information MiCOM P747 22 P747 TM EN 1 P747 TM EN 1 1...
Page 43: ...HARDWARE DESIGN CHAPTER 3...
Page 44: ...Chapter 3 Hardware Design MiCOM P747 24 P747 TM EN 1 P747 TM EN 1 1...
Page 74: ...Chapter 3 Hardware Design MiCOM P747 54 P747 TM EN 1 P747 TM EN 1 1...
Page 75: ...CONFIGURATION CHAPTER 4...
Page 76: ...Chapter 4 Configuration MiCOM P747 56 P747 TM EN 1 P747 TM EN 1 1...
Page 117: ...PROTECTION FUNCTIONS CHAPTER 5...
Page 118: ...Chapter 5 Protection Functions MiCOM P747 98 P747 TM EN 1 P747 TM EN 1 1...
Page 160: ...Chapter 5 Protection Functions MiCOM P747 140 P747 TM EN 1 P747 TM EN 1 1...
Page 161: ...MONITORING AND CONTROL CHAPTER 6...
Page 162: ...Chapter 6 Monitoring and Control MiCOM P747 142 P747 TM EN 1 P747 TM EN 1 1...
Page 211: ...SCADA COMMUNICATIONS CHAPTER 7...
Page 212: ...Chapter 7 SCADA Communications MiCOM P747 192 P747 TM EN 1 P747 TM EN 1 1...
Page 259: ...REDUNDANT ETHERNET CHAPTER 8...
Page 260: ...Chapter 8 Redundant Ethernet MiCOM P747 240 P747 TM EN 1 P747 TM EN 1 1...
Page 293: ...CYBER SECURITY CHAPTER 9...
Page 294: ...Chapter 9 Cyber Security MiCOM P747 274 P747 TM EN 1 P747 TM EN 1 1...
Page 313: ...SETTINGS APPLICATION SOFTWARE CHAPTER 10...
Page 314: ...Chapter 10 Settings Application Software MiCOM P747 294 P747 TM EN 1 P747 TM EN 1 1...
Page 322: ...Chapter 10 Settings Application Software MiCOM P747 302 P747 TM EN 1 P747 TM EN 1 1...
Page 323: ...BUSBAR COMMISSIONING TOOL CHAPTER 11...
Page 324: ...Chapter 11 Busbar Commissioning Tool MiCOM P747 304 P747 TM EN 1 P747 TM EN 1 1...
Page 330: ...Chapter 11 Busbar Commissioning Tool MiCOM P747 310 P747 TM EN 1 P747 TM EN 1 1...
Page 331: ...SCHEME LOGIC CHAPTER 12...
Page 332: ...Chapter 12 Scheme Logic MiCOM P747 312 P747 TM EN 1 P747 TM EN 1 1...
Page 348: ...Chapter 12 Scheme Logic MiCOM P747 328 P747 TM EN 1 P747 TM EN 1 1...
Page 349: ...INSTALLATION CHAPTER 13...
Page 350: ...Chapter 13 Installation MiCOM P747 330 P747 TM EN 1 P747 TM EN 1 1...
Page 361: ...COMMISSIONING INSTRUCTIONS CHAPTER 14...
Page 362: ...Chapter 14 Commissioning Instructions MiCOM P747 342 P747 TM EN 1 P747 TM EN 1 1...
Page 387: ...MAINTENANCE AND TROUBLESHOOTING CHAPTER 15...
Page 388: ...Chapter 15 Maintenance and Troubleshooting MiCOM P747 368 P747 TM EN 1 P747 TM EN 1 1...
Page 403: ...TECHNICAL SPECIFICATIONS CHAPTER 16...
Page 404: ...Chapter 16 Technical Specifications MiCOM P747 384 P747 TM EN 1 P747 TM EN 1 1...
Page 425: ...SYMBOLS AND GLOSSARY APPENDIX A...
Page 426: ...Appendix A Symbols and Glossary MiCOM P747 406 P747 TM EN 1 P747 TM EN 1 1...
Page 443: ...COMMISSIONING RECORD APPENDIX B...
Page 444: ...Appendix B Commissioning Record MiCOM P747 424 P747 TM EN 1 P747 TM EN 1 1...
Page 449: ...WIRING DIAGRAMS APPENDIX C...
Page 450: ...Appendix C Wiring Diagrams MiCOM P747 430 P747 TM EN 1 P747 TM EN 1 1...
Page 456: ...Appendix C Wiring Diagrams MiCOM P747 436 P747 TM EN 1 P747 TM EN 1 1...
Page 457: ......