10
GFK-2731
Chapter 10 Technical data and ordering data
10-3
Safety characteristics according to DIN EN 62061
Achievable SIL claim limit
SIL CL = SIL 2 (single-channel)
SIL CL = SIL 3 (two-channel)
Depends on the parameterization and wiring (see "Connection
options for actuators depending on the parameterization" on
page 2-5 and "Connection examples for safe outputs" on page 6-1)
Safe failure fraction (SFF)
99%
Probability of a dangerous failure per hour for the entire module
(PFH)
SIL CL 2: 1 % of 10
-6
, maximum (corresponds to 1 * 10
-8
)
SIL CL 3: 1 % of 10
-7
, maximum (corresponds to 1 * 10
-9
)
1 % of 10
-7
, maximum (corresponds to 1 * 10
-9
)
Depends on the parameterization (see Table 6-3 on page 6-3)
Hardware fault tolerance (HFT) of the module
1
Permissible duration of use
20 years
Safety characteristics according to EN ISO 13849-1
Achievable performance level
PL e (two-channel)
PL d (single-channel)
Depends on the parameterization and wiring (see "Connection
options for actuators depending on the parameterization" on
page 2-5 and "Connection examples for safe outputs" on page 6-1)
See also "Achievable safety depending on the modules used" on
Diagnostic coverage (DC)
99%
Mean time to dangerous failure (MTTFd)
For single-channel assignment: 100 years
For two-channel assignment: 100 years
Supply voltage U
L
(logic)
Current consumption
230 mA, maximum
The safety terminal is supplied with communications power via the bus coupler, a VersaPoint controller, or a designated
power terminal in the station. Potential routing is used for the communications power in the VersaPoint station. For tech-
nical data, please refer to the data sheet for the bus coupler, VersaPoint controller, or power terminal used.
Supply voltage U
M
(actuators)
Nominal voltage
24 V DC according to EN 61131-2 and EN 60204
Tolerance
-15%/+20% including an entire AC voltage component with peak value of 5%
Ripple
3.6 V
pp
Permissible voltage range
19.2 V DC to 30.0 V DC, ripple included
Current consumption
30 mA, typical (all outputs set) (plus actuator current)
The safety terminal is supplied with main voltage U
M
via the bus coupler, a VersaPoint controller, or a power terminal in the station. Potential
routing is used for the main voltage in the VersaPoint station. For technical data, please refer to the data sheet for the bus coupler,
VersaPoint controller, or power terminal used.
WARNING: Loss of the safety function when using unsuitable power supplies
Only use power supplies according to EN 50178/VDE 0160 (PELV).