User manual IC220SDL953 - September 2011
GFK-2731
2.9
Process data words
The module uses 8, 16, or 24 words in the VersaPoint system. How these words are
mapped is described in "Process image" on page A-13.
The input data only indicates the actual status of the outputs if no bus errors or device
errors are present. Even during the parameterized switch-off delay in stop category 1, the
status of the outputs on the module does not correspond to the status of the outputs on the
controller.
The parameterization of the outputs determines whether the input data is mapped in
single-channel or two-channel mode. The value for "parameterized output" for the outputs
is also set for the input data.
2.10 Programming data/configuration data
2.10.1
Local bus
2.10.2
Other bus systems or networks
Operating mode
VersaSafe
24 words
VersaSafe
16 words
VersaSafe multiplexer
ID code
ABhex (171dec)
AB
hex
(171
dec
)
AB
hex
(171
dec
)
Length code
18
hex
(24dec)
10
hex
(16
dec
)
08
hex
(08dec)
Input address area
Application-specific
Application-specific
Application-specific
Output address area
Application-specific
Application-specific
Application-specific
Parameter channel (PCP)
0 words
0 words
0 words
Register length
24 words
16 words
8 words
The programming data/configuration data is defined in the device description (FDCML,
GSD, GSDML, etc.) according to the bus or network used.