8
GFK-2731
Chapter 8 Errors: Messages and removal
8-3
Example: ANDing the
diagnostic code
Diagnostic code indicated: 0D03
hex
Diagnostic code specified in the documentation: X503
hex
LED
The "LED" column specifies which local diagnostic LEDs indicate the error.
Acknowledgment
To remove the error, evaluate the PUR and OAR bits in the diagnostic register of the
IC220SDL953 (see "Dev-Ack-x (device acknowledgment)" on page A-17). These specify
whether a power up is expected or whether an acknowledgment is required.
Errors that must be acknowledged are indicated with "Yes" in the "Acknowledgment"
column. Special conditions for re-enabling an output or the module are specified in
brackets [e.g., Yes (1)] in the "Acknowledgment" column and explained below the relevant
table.
Table 8-3
Relationship between the diagnostic code indicated and the diagnostic code specified in the
documentation
15
14
13
12
11
10
...
0
Assignment of the diagnostic
register (see page A-18)
COK
SA
E
PUR OAR
Diagnostic code
Diagnostic code
indicated
hex
0
D
0
3
bin
0
0
0
0
1
1
0
1
0
0
0
0
0
0
1
1
Mask (07FF
hex
)
bin
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
Diagnostic code in the
documentation
bin
0
0
0
0
0
1
0
1
0
0
0
0
0
0
1
1
hex
0 ->
X
(not relevant)
5
0
3
For information about acknowledging satellite errors, see "Acknowledgment of error