The LEDs on the Energy Pack indicate its status.
LED
LEDState
Energy Pack Status
IN
Green,
solid
Input power is applied and within the
specified range.
Red,
solid
Input power is outside the specified
range.
Off
Input power is not applied.
STAT
Green,
blinking
CapPack Charging in progress. No
faults.
Green,
solid
CapPack is fully charged and no faults.
Amber,
blinking
CapPack is nearing end-of-life. The
CapPack must be replaced soon.
Backup is still guaranteed.
Red,
blinking
Internal fault: Cycle power to the
Energy Pack. If this does not clear the
fault, contact Technical Support and
replace the Energy Pack.
Red,
solid
CapPack has reached end-of-life.
Replace the CapPack. Backup is
not
guaranteed.
Off
No power applied.
OUT
Green,
solid
Output power is within the specified
range.
Red,
solid
Output power is present but outside
spec.
Off
Output power is not present.