3 9
STATUS CODE
-47
D E S C R I P T I O N
No
MEMORY
R E C A L L
C O N T R O L
T Y P E
Traction
STATUS CODE
-46
D E S C R I P T I O N
Look ahead test for T2 volts. ( Greater than 85% of
battery volts)
No
MEMORY
R E C A L L
C O N T R O L
T Y P E
Traction
Figure 1
Figure 1
SYMPTOM
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Defective 1 REC.
Check for shorted 1 REC.
Check for defective 1 REC insulator (co-therm)
that may short 1 REC heat sink to base plate.
Defective 1A contactor.
Check for welded 1A contactor power tips.
SYMPTOM
Forward or reverse contactor will open and close, then
open and then can only be closed by opening and closing
the key switch.
POSSIBLE CAUSE
Defective 2 REC circuit.
Check that 2 REC will gate on.
Check for open circuit or loose connection
between 2 REC gate and PZ10. (white/red wire)
Check for open circuit or loose connection 1 REC
and 1C through the 2 REC circuit.
F or R contactor or power tips bouncing open.
Check that power tips on F and R contactor power
tips do not bounce open during operation (ie:
travel over speed bumps or dock plates).
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at T2 is
greater than 85% of battery volts.
STATUS INDICATION CRITERIA
This status code is displayed when the 2 REC fails to
turn on.
2REC does not turn properly
Summary of Contents for EV100 LX
Page 3: ...3 EV100LX COMPONENT LOCATIONS ...
Page 4: ...4 EV100LX OUTLINE DRAWING ...
Page 5: ...5 EV100LX WITH SPEED LIMIT AND FW 9 ...
Page 6: ...6 EV100LX WITH REGEN AND FW 9 ...
Page 7: ...7 EV100LX DUAL MOTOR CONTROL 9 ...
Page 8: ...8 EV100LX PUMP CONTROL 9 ...
Page 10: ...10 EV100LX PART NUMBER IDENTIFICATION ...
Page 60: ...6 0 ...
Page 80: ...g GE Industrial Systems EV200LX SUPPLEMENT Page 4 of 5 REV 11 2002 Wiring Diagram ...