60
PMCS Interface Toolkit
{ set the bus status for the incoming feeds to
the dependent bus below in the
distribution hierarchy. The IF_THEN
statements in this section traverse the
hierarchy from top to bottom, left to right,
and then bottom to top, right to left.}
bus6 = 0;
bus7 = 0;
{ two main feeds }
IF (bus1
AND brk1_s) THEN
bus3 = 1;
ENDIF;
IF (bus2
AND brk2_s) THEN
bus4 = 1;
ENDIF;
{ left to right across tie breaker }
IF (bus3
AND brk3_s) THEN
bus4 = 1;
ENDIF;
IF (bus4
AND brk4_s) THEN
bus5 = 1;
ENDIF;
{ two outgoing feeders }
IF (bus3
AND brk5_s) THEN
bus6 = 1;
ENDIF;
IF (bus5
AND brk6_s) THEN
bus7 = 1;
ENDIF;
{ back feed from two outgoing feeds }
IF (bus7
AND brk6_s) THEN
bus5 = 1;
ENDIF;
IF (bus6
AND brk5_s) THEN
bus3 = 1;
ENDIF;
{ right to left across tie breaker }
IF (bus5
AND brk4_s) THEN
bus4 = 1;
ENDIF;
IF (bus4
AND brk3_s) THEN
bus3 = 1;
ENDIF;
{ two incoming feeds }
IF (bus5 AND brk2_s) THEN
bus2 = 1;
ENDIF;
IF (bus3
AND brk1_s) THEN
bus1 = 1;
ENDIF;