6. ACCEPTANCE TESTS
GEK-106168E
DBF Breaker Failure Protection
33
6.9. FUNCTIONS
6.9.1 50BF 1P UNIT TEST
1.
Change setpoint GENERAL/FUNCTION PERMIT/50BF 1P FUNCTION to PER.
2.
Change setpoint GENERAL/FUNCTION PERMIT/50BF 3P FUNCTION to NO PER.
3.
Change setpoint TABLE 1/FUNCTION PERMIT/3P No INT FUNCT to NO PER.
4.
Change setpoint 50BF SETTINGS/Nº OUTPUT STAGES to 2.
5.
The precision timer will be started at the same time than the corresponding contact converter (digital input) is
energized. The timer stop input will be wired to any DBF contact under test, i.e. contact C4-D4.
6.
Apply 2A to terminals A1-A2 (phase A).
7.
Energize digital input CC1 PHASE A BF INITIATE (terminal C9-D10).
8.
Check that after T1 time delay (1s), the following contacts are closed:
A12-B12
C4-D4
C5-D5
In case the relay under test includes an expansion board, check also the operation of the following contacts:
E1-F1
E2-F2
E3-F3
9.
Check that after 2nd Stage Timer delay (2s), the following contacts are closed:
C1-D1
C6-D6
C7-D7
and if the relay is equipped with an expansion board also the following contacts must be closed:
E4-F4
E5-F5
E6-F6
10. Repeat steps 7, 8, 9 and 10 using phase B current (B1-B2 terminals) and CC2 PHASE B BF INITIATE (D9-
D10 terminals) to start the breaker failure operation.
11. Repeat steps 7, 8, 9 and 10 using phase C current (A3-A4 terminals) and CC3 PHASE C BF INITIATE (C10-
D10 terminals) to start the breaker failure operation.
12. Change setpoint TABLE 1/50BF SETTINGS/Nº OUTPUT STAGES to 1.
13. Repeat steps 7 to 12 to check that in this case contacts C1-D1, C6-D6, C7-D7, E4-F4, E5-F5 and E6-F6 close
at the same time than contacts: A12-B12, C4-D4, C5-D5 and E1-F1, E2-F2, E3-F3 (if an expansion board is
available).
Summary of Contents for DBF
Page 3: ......
Page 7: ...LIST OF FIGURES iv DBF Breaker Failure Protection GEK 106168E ...
Page 27: ...3 SETTINGS 20 DBF Breaker Failure Protection GEK 106168E ...
Page 31: ...4 TECHNICAL CHARACTERISTICS 24 DBF Breaker Failure Protection GEK 106168E ...
Page 45: ...6 ACCEPTANCE TESTS 38 DBF Breaker Failure Protection GEK 106168E ...
Page 47: ...7 INSTALLATION AND MAINTENANCE 40 DBF Breaker Failure Protection GEK 106168E ...
Page 57: ...8 KEYBOARD AND DISPLAY 50 DBF Breaker Failure Protection GEK 106168E ...
Page 58: ...FIGURES GEK 106168E DBF Breaker Failure Protection 51 FIGURES FIGURES FIGURES FIGURES ...
Page 61: ...FIGURES 54 DBF Breaker Failure Protection GEK 106168E FIGURE 3 FRONT VIEW 226B7412 H9 ...
Page 62: ...FIGURES GEK 106168E DBF Breaker Failure Protection 55 FIGURE 4 REAR VIEW 226B7412H10 ...
Page 63: ...FIGURES 56 DBF Breaker Failure Protection GEK 106168E FIGURE 5 DIMENSIONS DIAGRAM 226B6086H10 ...
Page 64: ...FIGURES GEK 106168E DBF Breaker Failure Protection 57 FIGURE 6 PANEL DRILLING 226B6086H10 ...