6. ACCEPTANCE TESTS
36
DBF Breaker Failure Protection
GEK-106168E
8.
Check that after 3P NO I TIMER T3 (2s), the following contacts are closed:
A12-B12
C1-D1
C4-D4
C6-D6
C5-D5
C7-D7
9.
If the relay is provided with an expansion board, check that also the following contacts are closed:
E1-F1
E2-F2
E3-F3
E4-F4
E5-F5
E6-F6