2. OPERATION LOGIC
GEK-106168E
DBF Breaker Failure Protection
5
2.2. MONITORING AND RECORDING FUNCTIONS
2.2.1 MEASUREMENT
The DBF system provides the continuous measurement of phase and ground current values.
These measurements can be accessed directly on the liquid crystal display (HMI) on the front of the relay, or via
the GE-LOCAL communication software.
2.2.2 ASSOCIATED BREAKER STATUS
The DBF system monitors the associated breaker status through the digital inputs 52/b (or 52/a), and it is
displayed on the local HMI or through the communications software.
2.2.3 TARGET LAMPS
The DBF incorporates 17 LED target lamps, one fixed LED (two colors) assigned to the system ready function,
and 16 user configurable red LEDs. These configurable LEDs are arranged in two columns of 8 LEDs each. The
configuration is done using the GE-INTRO software, and it consists on assigning an internal event (or an AND
gate of internal events) to an LED. The LED can be configured to have memory (if Vdc is removed or the event
causing the operation of the LED gets deactivated) or not and to blink or to be steady. The internal events must
be previously defined using the internal signals of the relay. It is possible to use AND, OR and NOT logic gates to
define these events. The available internal signals are listed in the following table.
The TARGET RESET button allows testing all target lamps if it is pushed for a short time (lighting up all of them),
or resets the sealed-in targets if it remains pressed for three seconds or more.
Please refer to GE_INTRO (configuration software) Instruction book (GEK-105594) for further information.
INTERNAL PROTECTION STATUS SIGNALS
Group
Status
Comment
1.0
Program Initiate
Relay starts running (Vdc just applied).
1.1
Settings change
User changes any setting
1.2
Write Counters
User sets a value for any counter
1.3
Configuration Change
User changes relay configuration
1.4
External Trigger
Oscillography triggered by Dig. Input
1.5
Communications Trigger
Osc. triggered by HMI or GE_LOCAL
1.6
Reset Operation
Latched Relays Reset received
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15
2.0
Input Nº 1
Digital Input #1 Status
2.1
Input Nº 2
Digital Input #2 Status
2.2
Input Nº 3
Digital Input #3 Status
2.3
Input Nº 4
Digital Input #4 Status
2.4
Input Nº 5
Digital Input #5 Status
2.5
Input Nº 6
Digital Input #6 Status
2.6
Summary of Contents for DBF
Page 3: ......
Page 7: ...LIST OF FIGURES iv DBF Breaker Failure Protection GEK 106168E ...
Page 27: ...3 SETTINGS 20 DBF Breaker Failure Protection GEK 106168E ...
Page 31: ...4 TECHNICAL CHARACTERISTICS 24 DBF Breaker Failure Protection GEK 106168E ...
Page 45: ...6 ACCEPTANCE TESTS 38 DBF Breaker Failure Protection GEK 106168E ...
Page 47: ...7 INSTALLATION AND MAINTENANCE 40 DBF Breaker Failure Protection GEK 106168E ...
Page 57: ...8 KEYBOARD AND DISPLAY 50 DBF Breaker Failure Protection GEK 106168E ...
Page 58: ...FIGURES GEK 106168E DBF Breaker Failure Protection 51 FIGURES FIGURES FIGURES FIGURES ...
Page 61: ...FIGURES 54 DBF Breaker Failure Protection GEK 106168E FIGURE 3 FRONT VIEW 226B7412 H9 ...
Page 62: ...FIGURES GEK 106168E DBF Breaker Failure Protection 55 FIGURE 4 REAR VIEW 226B7412H10 ...
Page 63: ...FIGURES 56 DBF Breaker Failure Protection GEK 106168E FIGURE 5 DIMENSIONS DIAGRAM 226B6086H10 ...
Page 64: ...FIGURES GEK 106168E DBF Breaker Failure Protection 57 FIGURE 6 PANEL DRILLING 226B6086H10 ...