2. OPERATION LOGIC
14
DBF Breaker Failure Protection
GEK-106168E
2.4.3.2 Outputs
The basic DBF system has 10 outputs as follows:
•
2 tripping contacts (A12-B12 and C1-D1)
•
1 Breaker failure pickup signaling (A11-B11)
•
1 Internal arc detection (C2-D2)
•
1 Equipment alarm (C3-D3)
•
5 configurable contacts (C4-D4 to C8-D8)
The optional expansion board for the DBF provides 6 additional latched contacts (E1-F1 to E6-F6). This outputs
are not configurable and are assigned as follows:
•
3 tripping contacts (TRIP 1st Stage) (E1-F1 to E3-F3)
•
3 tripping contacts (TRIP 2nd Stage) (E4-F4 to E6-F6)
The configurable outputs can be programmed using logic based on the internal protection states (pick-ups, trips,
alarms, etc.). The DBF has 66 different internal states, and these can be used to carry out logical operations NOT,
AND and OR, which gives the unit a great flexibility.
The output configuration is done using different levels. At the first level it is possible to use AND gates of up to 16
signals. The output is incorporated into the states matrix so that it can then be used in other AND gates of up to 16
inputs. This process can continue until the 16 ANDs are used.
Once the AND gates have been configured it is possible to create a second level with OR gates of 16 inputs
limited to the established groups of bytes, and whose logical outputs are assigned to physical outputs of the unit.
This means that we can configure the physical outputs with any internal signal from the status or any combination
of them made by means of the AND logic gates.
Summary of Contents for DBF
Page 3: ......
Page 7: ...LIST OF FIGURES iv DBF Breaker Failure Protection GEK 106168E ...
Page 27: ...3 SETTINGS 20 DBF Breaker Failure Protection GEK 106168E ...
Page 31: ...4 TECHNICAL CHARACTERISTICS 24 DBF Breaker Failure Protection GEK 106168E ...
Page 45: ...6 ACCEPTANCE TESTS 38 DBF Breaker Failure Protection GEK 106168E ...
Page 47: ...7 INSTALLATION AND MAINTENANCE 40 DBF Breaker Failure Protection GEK 106168E ...
Page 57: ...8 KEYBOARD AND DISPLAY 50 DBF Breaker Failure Protection GEK 106168E ...
Page 58: ...FIGURES GEK 106168E DBF Breaker Failure Protection 51 FIGURES FIGURES FIGURES FIGURES ...
Page 61: ...FIGURES 54 DBF Breaker Failure Protection GEK 106168E FIGURE 3 FRONT VIEW 226B7412 H9 ...
Page 62: ...FIGURES GEK 106168E DBF Breaker Failure Protection 55 FIGURE 4 REAR VIEW 226B7412H10 ...
Page 63: ...FIGURES 56 DBF Breaker Failure Protection GEK 106168E FIGURE 5 DIMENSIONS DIAGRAM 226B6086H10 ...
Page 64: ...FIGURES GEK 106168E DBF Breaker Failure Protection 57 FIGURE 6 PANEL DRILLING 226B6086H10 ...