2. OPERATION LOGIC
12
DBF Breaker Failure Protection
GEK-106168E
2.4. CONTROL
2.4.1 TABLES OF SETTINGS
The DBF system has two types of settings stored in non-volatile memory (information is kept even when there is
no auxiliary voltage):
•
Generic Settings.
•
Specific Settings.
The
Generic settings are grouped as follows:
GENERAL SETTINGS
BREAKER SETTINGS
ACTIVE TABLE SETTINGS
OSCILLOGRAPHY MASK
FUNCTION PERMISSION
For the
specific settings, the DBF allows to have up to 3 independent setting tables. These specific settings are
grouped as follows:
50BF SETTINGS
INTERNAL ARC SETTINGS
Only one setting table is active at a given time, and this is the table used by the system to run the different
functions included in it.
There is an "ACTIVE TABLE" setting that determines the settings table that is active at a given moment.
The active settings table can be changed by means of up to 2 digital inputs, referred to as "ACTIVE TABLE
SELECT 0" and "ACTIVE TABLE SELECT 1" which allow up to 4 combinations from 0 to 3. To do this it is
necessary to configure (using GE-INTRO software) two inputs to have these meanings. For applications which
require less tables (up to 2) it is possible to use only one input.
The selected combination is obtained from the binary coding of the 2 inputs mentioned (see following table). The
0-0 means selecting the table indicated in the "ACTIVE TABLE" setting, and numbers 0-1 to 1-1 select tables 1 to
3 respectively
Table Selection
INPUT-1
Table Selection
INPUT-0
Active Table
0
0
Selected by setting
0
1
1
1
0
2
1
1
3
NOTE: if the inputs are programmed and used, energizing them, this selection has priority over the "ACTIVE
TABLE" setting and the table which is in fact used is determined by the status of the digital inputs.
Summary of Contents for DBF
Page 3: ......
Page 7: ...LIST OF FIGURES iv DBF Breaker Failure Protection GEK 106168E ...
Page 27: ...3 SETTINGS 20 DBF Breaker Failure Protection GEK 106168E ...
Page 31: ...4 TECHNICAL CHARACTERISTICS 24 DBF Breaker Failure Protection GEK 106168E ...
Page 45: ...6 ACCEPTANCE TESTS 38 DBF Breaker Failure Protection GEK 106168E ...
Page 47: ...7 INSTALLATION AND MAINTENANCE 40 DBF Breaker Failure Protection GEK 106168E ...
Page 57: ...8 KEYBOARD AND DISPLAY 50 DBF Breaker Failure Protection GEK 106168E ...
Page 58: ...FIGURES GEK 106168E DBF Breaker Failure Protection 51 FIGURES FIGURES FIGURES FIGURES ...
Page 61: ...FIGURES 54 DBF Breaker Failure Protection GEK 106168E FIGURE 3 FRONT VIEW 226B7412 H9 ...
Page 62: ...FIGURES GEK 106168E DBF Breaker Failure Protection 55 FIGURE 4 REAR VIEW 226B7412H10 ...
Page 63: ...FIGURES 56 DBF Breaker Failure Protection GEK 106168E FIGURE 5 DIMENSIONS DIAGRAM 226B6086H10 ...
Page 64: ...FIGURES GEK 106168E DBF Breaker Failure Protection 57 FIGURE 6 PANEL DRILLING 226B6086H10 ...