background image

CHAPTER 5: CONFIGURING THE SOFTWARE

D20MX HARDWARE USER’S MANUAL

GE INFORMATION

63

NOTE

The D20MX can only be accessed over the front RS232 port with the system default 
configuration.

If you synchronize a configuration with any of the following errors:

There are no usernames configured in the B014 User table,

The B014 User table is disabled, or

The B014 application definition does not match the firmware version, 

then the applications do not start and you only have serial access in debug mode.
Login with the system default username over the front RS232 port and synchronize a 
correct configuration.

Download image files to the D20MX

When to download

Instances where you may need to download an operating system or application image file 
to your D20MX:

When a new version of the operating system or application image has been released.

If the D20MX has performed self-diagnostics and determined that the application 
image file is either missing or corrupted.

After maintenance or replacement work that has deleted the application file.

Prerequisites for image download

The following items must be available before an application or operating system image file 
can be loaded into a D20MX over a serial or network link:

Windows PC with SGConfig version 7.2 and higher software.

The application firmware file, preferably located on a local hard drive.
This file will be named: appl.out.

The operating system image file, preferably located on a local hard drive.
This file will be named: vxWorks.

The D20MX module must be installed into a D20 chassis, ready to power-up.

Prerequisite for image 

download over a 

serial link

The following item must be available before an application and operating system image 
file can be loaded into a D20MX over a serial link:

A NULL modem cable (GE Energy part number 977-0529) connecting the RS-232 
connector on the front panel of the D20MX to the serial communications port of a PC 
or terminal. 

Prerequisite for image 

download over a 

network link

The following items must be available before an application and operating system image 
file can be loaded into a D20MX over the network:

An Ethernet switch and appropriate Ethernet patch cables to connect your PC's 
Network Adapter and the D20MX's Ethernet port 1 to the switch.

The D20MX contains a configuration file with LAN enabled and an IP address that 
matches the one configured in SGConfig.

The PC's Network Adapter is configured with an IP address on the same network as 
the IP address of the D20MX.

Summary of Contents for D20MX

Page 1: ...GE Digital Energy GE Information D20MX Processor Hardware User s Manual 994 0140 Version 1 20 Revision 0...

Page 2: ...s a registered trademark of ERNI Elektroapparate GMBH Hyperterminal is a registered trademark of Hil graeve Tera Term is a registered trademark of T Teranishi Incorporated IEC is a registered trademar...

Page 3: ...t customer support 11 Product returns 12 Upgrade your D20MX processor firmware 12 BEFORE YOU START Safety precautions 13 Warning symbols 14 Regulatory compliance information 15 CE Mark compliance 15 P...

Page 4: ...32 switch panel operation 52 Redundancy wiring diagrams 52 POWERING UP AND TESTING Required for testing 55 Accessing WESMAINT II using a terminal 56 Terminal Emulation 56 SHELL 56 Power up and test st...

Page 5: ...NG THE D20MX Front panel LEDs 85 Operational status LEDs 85 LAN port status LEDs 86 Fiber optic port status LEDs 86 SERVICING THE D20MX Performing periodic inspection 87 Removing the D20MX processor m...

Page 6: ...6 GENERAL D20MX HARDWARE USER S MANUAL TABLE OF CONTENTS...

Page 7: ...ce of SCADA equipment This manual assumes that the user is experienced in Electrical utility applications Electrical wiring and safety procedures Related other manufacturers products such as protectiv...

Page 8: ...conventions are used throughout this manual Bold face is used for Names of software program menus editors and dialog boxes also for the names of menu commands keyboard keys icons and desktop shortcuts...

Page 9: ...age or downtime The following safety and equipment symbols are used in this document Indicates a hazardous situation which if not avoided will result in death or serious injury Indicates a hazardous s...

Page 10: ...10 GE INFORMATION D20MX HARDWARE USER S MANUAL ABOUT THIS DOCUMENT...

Page 11: ...Center is open 24 hours a day seven days a week for you to talk directly to a GE representative In the U S and Canada call toll free 1 800 547 8629 International customers please call 1 905 927 7070...

Page 12: ...will be sent the RMA number and RMA documents via fax or e mail Once you receive the RMA documents attach them to the outside of the shipping package and ship to GE NOTE Product returns will not be a...

Page 13: ...cessor card is a pin for pin compatible replacement for all generations of the D20 SBC providing the latest revisions of common D20 applications and performance enhancements to support NERC compliant...

Page 14: ...al safety shield All electronic components within the D20MX are susceptible to damage from electrostatic discharge To prevent damage when handling this product use approved static control procedures H...

Page 15: ...to try to correct the interference by one or more of the following measures Reorient or relocate the receiving device Increase the separation between the equipment Connect the equipment into an outle...

Page 16: ...RBAC keeping operator and engineering activities separated logged and simple NERC compliant passwords with strong complexity rules and one way encrypted Full auditing including Syslog integration to...

Page 17: ...col Has the ability to function as several distinct IEC 60870 5 101 104 RTUs Supports the unbalanced version of the data link 906 New 001 A113N PSR DCA for D20MX Programmable Synchrocheck Relay PSR DC...

Page 18: ...g control commands to the remote devices and processing data autonomously collected by the data link layer 210 New B071 0 WESMAINT File Upload Uploads files via the WESMAINT port as S records or using...

Page 19: ...Peripheral Board supports B003 D20A Peripheral Board Code 301 S034 D20K Peripheral Board supports B003 D20K Peripheral Board Code 306 S035 D20C Peripheral Board supports B003 D20C Peripheral Board Cod...

Page 20: ...witch and fuses This chassis contains the WESTERM D20M SS termination panel which is attached directly to the back of the assembly see Figure 2 Figure 2 D20 non VME backplane D20 non VME Chassis Power...

Page 21: ...is see Figure 4 contains the WESTERM D20M termination panel that is mounted separately on the D20 chassis The VME chassis kit includes a VME bus backplane called the WESTERM D20VME The VME bus backpla...

Page 22: ...e to the D20MX may occur The required fuse rating depends on the power consumption of your system The D20 available power supplies listed in Table 7 are equipped with two field replaceable fuses see F...

Page 23: ...ssor They are configured as slaves to the D20MX processor board In this way specific I O processing is distributed throughout the RTU to the appropriate I O module There are five types of I O peripher...

Page 24: ...ply 20 60VDC Input 24V ISO Output A B D20 Power Supply 20 60VDC Input 48V ISO Output B C D20 Power Supply 100 300VDC 85 264VAC Input 24V ISO Output C D D20 Power Supply 100 300VDC 85 264VAC Input 48V...

Page 25: ...assis A C D20MX CPU only C D20MX CPU Options A D20MX non VME dual 10 100 1000BASE TX Ethernet Ports front access A C D20MX non VME dual 100BASE FX Ethernet Ports front access C G D20MX non VME dual 10...

Page 26: ...526 3104 D20MX 100Base FX Rear ST FO Card 1 975 1236 D20MX CPU to D20MX Rear FO Card Harness 1 975 1237 Termination panel to Backplane 0 V Harness 1 1 1 953 1014 Blank Plate for D20MX Install 1 1 1 9...

Page 27: ...ernet interface Twisted Pair 10 100 1000BaseT Isolated RJ 45 connector 100BaseFX Fiber Optic 1300 nm 50 125 m 62 5 125 m multi mode duplex fiber cable ST connectors Serial communications D 20 Link 2 c...

Page 28: ...ods of time as this will shorten the life of the super capacitor and reduce the backup time of the real time clock Humidity rating 5 to 95 relative humidity non condensing Environmental rating Ingress...

Page 29: ...Relative humidity 5 to 95 non condensing Maximum altitude 12192 m 40 000 feet above sea level NOTE Do not store the D20MX above 60 C for extended periods of time as this will shorten the life of the s...

Page 30: ...30 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 1 BEFORE YOU START...

Page 31: ...Grounding the D20MX and connecting the power supply D20 chassis layouts Installation of the D20MX can be performed with one of three D20 chassis layouts see Installation steps on page 33 The D20 non V...

Page 32: ...Ethernet connectors Figure 7 D20 chassis front panel D20MX with front fiber optic connectors D20 chassis D20 power supply D20MX processor D20MX cover plate D20MX cover plate filler Protective earth t...

Page 33: ...0MX must be placed on an anti static surface while not installed in the chassis 3 Remove all horizontal blank faceplates 4 Gently install the D20MX in the first bottom most slot Align the edge of the...

Page 34: ...of the D20MX or the backplane of the D20 chassis 11 If the D20MX is being installed in a VME chassis connect the 0 V cable part number 975 1237 11 1 Connect the bare end of the cable wire to the O V c...

Page 35: ...g limitations exist You cannot install multiple D20MX processor boards in a single D20 Therefore a maximum of seven serial and two D 20 Link connections are supported on each D20 unit The D20MX suppor...

Page 36: ...the 0 V cable wire to the O V connector on the WESTERM terminal block TB2 9 8 2 Remove the wire from the lower 0 V connector on the VME backplane and connect this wire to the male end of the 0 V cable...

Page 37: ...MX Non VME with Dual 100Base FX Fiber Optic Card part number 526 3005 multi mode duplex fiber cable ST connectors Flathead screwdriver with 0 6 mm by 3 5 mm blade for terminal block wiring 1 Phillips...

Page 38: ...mber 526 3001 or 526 3003 or 526 3005 For 526 3005LF only D20MX to Fiber Card Harness 975 1236 D20MX 100BASE FX Rear LC FO Card part number 526 3103LF or D20MX 100BASE FX Rear ST FO Card part number 5...

Page 39: ...D20MX HARDWARE USER S MANUAL GE INFORMATION 39 7 and 8 can be used externally for status wetting contact wetting and or miscellaneous power connections if applicable Figure 13 WESTERM D20M SS power s...

Page 40: ...40 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 2 INSTALLING THE D20MX...

Page 41: ...n the D20MX processor module D20MX front panel connectors The D20MX front panel can have one of the following layouts Ethernet connectors RJ45 see Figure 14 Front access Fiber optic connectors ST see...

Page 42: ...onal Status LEDs USB Port not supported Port Status LEDs Fiber Optic Port 2 Fiber Optic Port 1 RS232 Serial Port Operational Status LEDs USB Port not supported Fiber Optic Port Status LEDs Fiber Optic...

Page 43: ...with all 7 serial ports running at 19200 baud with 20 CPU utilization Refer to application configuration guides for supported baud rates and for data bits To avoid burning out the WESTERM or D20MX mai...

Page 44: ...straight through or crossover cable NOTE External switches must have Spanning Tree Protocol port settings configured to edge for proper operation To connect the D20MX to network devices Plug network...

Page 45: ...he following glass optical fiber GOF cabling with the D20MX 50 125 m core cladding multi mode gradient index cable 62 5 125 m core cladding multi mode gradient index cable 100 140 m core cladding mult...

Page 46: ...dancy enable only LAN A in the device properties of the D20MX To configure a system for dual IP redundancy enable both LAN A and LAN B in the device properties of the D20MX The D20MX device properties...

Page 47: ...name and host address Construct the host name by replacing the last two characters of the D20 Host Name with a two character suffix that matches the derived IP address you wish to override or disable...

Page 48: ...Active D20MX applications are operational Active CCU YES Standby D20MX applications are not operational but are ready to take over on a switchover command or a failover Standby CCU YES Disabled D20MX...

Page 49: ...w communication to the D20MX Use only a standard WESMAINT cable GE Energy part number 977 0300 when connecting to the rear panel COM0 connector Use of a NULL modem cable will cause permanent damage to...

Page 50: ...erial field connections to the Standby CCU which now becomes the Active CCU If CCU A fails CCU B becomes active See Figure 20 Redundant D20 system If CCU A fails Figure 20 Redundant D20 system If CCU...

Page 51: ...ystem you need the components listed in Table 21 Table 21 Redundant D20 system required components NOTE Pins 4 on switch panel connectors J2 through J9 are tied together and to the panel s power suppl...

Page 52: ...o the serial ports on the RS 232 switch panel P1 through P8 are connected to the first D20 P9 through P16 are connected to the second D20 Connections from the switch panel to both D20 units should be...

Page 53: ...56 7R 0 6 V DLO 7 3RZHU 6XSSO SDUW QR 9 RU 9 9 DEOH DVVHPEO SDUW QR 5HG ODFN UHHQ 1RW XVHG DEOH SDUW QR HYLFH 6HULDO 3RUW HYLFH 6HULDO 3RUW 7R 0 6HULDO 3RUW 7R 0 6HULDO 3RUW 7 DEOH SDUW QR UHHQ HOORZ...

Page 54: ...54 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 3 CONNECTING TO DEVICES AND NETWORKS...

Page 55: ...ile must be loaded into the D20MX NVRAM If you have replaced the main board of the D20MX then you will need to restore the configuration file so that diagnostic tests can be performed If this power up...

Page 56: ...Microsoft Windows does not have these limitations and is therefore recommended as a terminal emulation program It can be downloaded from the Internet SHELL The SHELL is a debugging and diagnostics too...

Page 57: ...automatically boots up when the power is switched on Internal processes perform a series of routines Self diagnostic tests are performed followed by the spawning of all the software applications that...

Page 58: ...ctioning correctly To check that CCU A and CCU B are communicating once you have powered up the Primary and Secondary units 1 On the front of the RS 232 Panel check that CCU A LED is illuminated which...

Page 59: ...of software failure 1 On the front of the RS 232 Panel check that CCU A LED is illuminated which shows that CCU A is Active NOTE Both the PWR A and PWR B LEDs should be illuminated 2 Connect a NULL m...

Page 60: ...ns port of the PC or terminal 3 Login to WESMAINT II through the emulator you are using Result The WESMAINT Main Menu is displayed 4 If you can login to WESMAINT II this indicates that CCU B is the Ac...

Page 61: ...D20MX firmware definition Introduction to the D20MX software The D20MX main processor board requires three valid files to be loaded An operating system image file called vxWorks which resides in the...

Page 62: ...for the default role based access control model provided with the D20MX default configurations In the event all configured RADIUS servers are down or if RADIUS is not configured the D20MX authenticate...

Page 63: ...ting system image file can be loaded into a D20MX over a serial or network link Windows PC with SGConfig version 7 2 and higher software The application firmware file preferably located on a local har...

Page 64: ...ome to SGConfig screen appears 3 Open a project containing a D20MX device Result The project s Main Page appears 4 Click on a D20MX device Result The ribbon changes to include the Communications group...

Page 65: ...from the Baud Rate drop down list 4 3 Click OK Result Tera Term main window appears and is communicating at 115 200 baud 5 Download the application image file 5 1 Press Enter to verify that communicat...

Page 66: ...e selected dialog checkbox Do not show this message again some of the following steps do not appear Accordingly ignore the affected steps 1 Connect Ethernet port 1 of the D20MX to the Ethernet switch...

Page 67: ...lt Warning message appears and confirmation to continue is requested 23 Acknowledge the warning and click Yes to continue or No to abort the operation Result If Yes is selected then refer to the follo...

Page 68: ...storage files 3 If the integrity check of the Primary storage files fails the D20MX tests the integrity of the firmware files in the Secondary 4 If the integrity of the Secondary storage files is val...

Page 69: ...shut off the power to the D20MX while the copy operation is in progress If power to the D20MX is disrupted during the copy operation the firmware will likely be corrupted 5 Once the copy operation ha...

Page 70: ...00 device configuration follow the steps in the following sections Section Transferring a D200 configuration to the D20MX on page 77 Section Transferring a D20 configuration to the D20MX on page 70 Tr...

Page 71: ...files SAG0001 02 zip and SAG0002 02 zip appear in the dialog 3 4 Select the appropriate file based on your decision in step 2 3 5 Click OK Result On completion a pop up message appears e g Project SAG...

Page 72: ...the D20MX Factory Default Configuration i e SAG0001 or SAG0002 8 1 Click GE Close Project Result The Close Project window appears 8 2 Select SAG0001 02 or SAG0002 02 8 3 Click OK 9 Open the SGConfig p...

Page 73: ...ree D20MX processor type part numbers 526 3001 526 3003 or 526 3005 12 9 Click OK Firmware tab and Select 12 10 Select either SAN0001 002 or SAN0002 002 as per the decision taken in step 2 If you had...

Page 74: ...directory dialog appears 15 4 Browse to the folder containing the exported RADIUS Role Table select the file named B014RADR CSV and click Open Result The WESMAINT II table icon set re appears 15 5 Do...

Page 75: ...M0 to 19 2K 17 1 Click the Project tab of the original D20 device configuration 17 2 Double click the D20 device Result The Application List popup appears 17 3 Double click the WESMAINT II application...

Page 76: ...e group Communications Options Result The Device Communication Options widow appears 21 4 Click Interface tab Connection Type 21 5 Select Direct Serial and change the Communications Port to the serial...

Page 77: ...he application configurations on the first processor This is manually resolved by moving applications from other processors to the first processor using the SGConfig device editing functions BEFORE co...

Page 78: ...irmware definition with ConfigPro Prerequisites Before you can update the firmware definition of a D20 device configuration the following components must be present ConfigPro 5 03 or higher installed...

Page 79: ...Result The two files 10730 02 zip and 10731 02 zip appear in the dialog 13 Select the appropriate file based on your decision made in the second step and click the Select button Result The Restore Pr...

Page 80: ...copy of your project 29 1 Select from the menu bar Project Copy Project Result The Copy Project dialog appears 29 2 In the From area navigate to the folder and select the project you want to transfer...

Page 81: ...ter Procedure Migrating a multi processor D200 will only transfer the application configurations on the first processor This is manually resolved by moving applications from other processors to the fi...

Page 82: ...n image file will have more groups Use the D20M Shell command swlic report to view the list of application groups swlic list to view the applications in each group Enable trial period An application g...

Page 83: ...on multiple D20MXs Unlock code If Customer Service send an unlock code use the D20M Shell command swlic unlock l unlock code to unlock the application group For example D20M swlic unlock l 6E62385170...

Page 84: ...nd CL Copy License to process the batch file This command processes the ram batch lic file extracting the appropriate license block and creates a new license file license lic If there are no errors th...

Page 85: ...e front panel become active The indicators provide status information on the operation of the D20MX Operational status LEDs The status LEDs indicate the unit s operational status LED Display Label Col...

Page 86: ...ing for up to a minute before turning off Green Normally off reserved for future expansion LED Display Label Color Status Description IRIG PWR RDY IRIG PWR RDY IRIG PWR RDY LED Display Label Color Sta...

Page 87: ...u are sufficiently grounded to prevent ESD damage to the D20MX or other components See section Grounding the D20MX on page 38 To remove the D20MX from a D20 chassis 1 Power down the D20 and disconnect...

Page 88: ...protective packaging 7 Grasp the D20MX by the front handles and slide the processor module all the way out of the D20 chassis Allow the D20MX to cool before removing The heatsink of the D20MX may be e...

Page 89: ...fault configurations SAG0001 and SAG0002 include a default role based access control model that meets the general rules shown in Table 22 Table 22 General access control rules The Shell access level r...

Page 90: ...a Link Display 32013 Table 36 Read Table 37 Modify Modbus DCA Display 59 Table 38 Read Table 39 Modify Modbus DPA Display 68 Table 40 Read Table 41 Modify File Upload Interface 32071 Table 42 Read Tab...

Page 91: ...sed Yes Yes No No Bit Position Description Administrator 2 Engineer 1 Operator 3 Observer 0 0 Time and Date display Yes Yes Yes Yes 1 Peripheral Status display Yes Yes Yes Yes 2 Peripheral Status Deta...

Page 92: ...n Administrator 2 Engineer 1 Operator 3 Observer 0 0 31 Not Used Yes Yes Yes No Bit Position Description Administrator 2 Engineer 1 Operato r 3 Observer 0 0 D20 AC Main Menu Yes Yes Yes Yes 1 Circuit...

Page 93: ...rator 2 Engineer 1 Operator 3 Observer 0 0 DNP DPA Display Yes Yes Yes Yes 1 22 Not Used Yes Yes Yes No 23 Configuration Pages Yes Yes Yes Yes 24 Detail Pages Yes Yes Yes No 25 31 Not Used Yes Yes Yes...

Page 94: ...server 0 0 31 Not Used Yes Yes Yes No Bit Position Description Administrator 2 Engineer 1 Operator 3 Observer 0 0 Any Page Yes Yes Yes Yes 2 31 Not Used Yes Yes Yes No Bit Position Description Adminis...

Page 95: ...n Description Administrator 2 Engineer 1 Operato r 3 Observer 0 0 Main Display Yes Yes Yes Yes 1 Analog Input Display Yes Yes Yes Yes 2 ADC Reference Display Yes Yes Yes Yes 3 Indication SOE or Digita...

Page 96: ...Yes Yes 1 Port Assignment and Cross References Displays Yes Yes Yes Yes 2 Current Status Display Yes Yes Yes Yes 3 Digital Output Display Yes Yes Yes Yes 4 Accumulator Display Yes Yes Yes Yes 5 Analo...

Page 97: ...ame Description Test Specification EN55011 CISPR 11 1 ISM RF equipment Electromagnetic disturbance characteristics Radiated Emissions 30 MHz to 1 GHz Conducted Emissions 150 kHz 30 MHz Standard Name D...

Page 98: ...on Test Specification IEC 61010 1 Safety requirements for electrical equipment for measurement control and laboratory use General requirements IEC 60255 5 Insulation coordination for measuring relays...

Page 99: ...mp 460 0073 supplied must be installed on the power cable IEC 60068 2 31 Drop and topple Dropping on each face Dropping on each corner Toppling or pushover For a total of 12 drops IEC 60068 2 78 Humid...

Page 100: ...100 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX B STANDARDS PROTECTION...

Page 101: ...hat is capable of handling current and future processing needs particularly for security The D20MX has 1 GB of RAM compared to 1 MB RAM in the D20ME The D20MX has 16 MB of built in NVRAM compared to t...

Page 102: ...Part number for the zero volt wire cable is 975 1237 D20 Non VME chassis 500 0305 Release 18 or higher Q Are the PCOMMON versions compatible with the D20MX A The following PCOMMON versions are compati...

Page 103: ...ing ConfigPro This appendix describes how to transfer a D20 configuration to the D20MX using ConfigPro Refer to the Application definition files and default configurations on page 128 to see how appli...

Page 104: ...D20 configurations to the D20MX To transfer a D20 configuration to the D20MX using ConfigPro 1 Create a D20MX device 1 1 Right click the D20 device 1 2 Select Copy Result The Select Project and Page...

Page 105: ...ns These applications are referred to as unused applications in the steps to follow 2 6 Click the Door icon to close the Application List report Result The project containing the created D20MX device...

Page 106: ...onfigPro 6 or 7 when prompted to upgrade select Yes By restoring the factory D20MX device to the same project location as the renamed D20 D20MX device in step 1 3 this will eliminate the need to copy...

Page 107: ...hin the project s main page and click on Firmware to confirm that the SAN0001 02 firmware has been automatically added to the list of firmware within the firmware library then proceed to step 3 4 3 3...

Page 108: ...own above the device properties of the factory default configuration 10730 02 uses SAN0001 3 3 4 Right click on the factory default configuration s main page and select Firmware 3 3 5 Select the requi...

Page 109: ...FORMATION 109 This is the location of the copy of the D20 device being modified In step 1 this D20 device was copied and renamed as a D20MX device Result The D20MX device location now has a firmware l...

Page 110: ...y 3 4 1 Right click on the D20MX device 3 4 2 Select the Processor tab Firmware tab Use Firmware Type check box to choose the SAN0001 firmware Result The Select a Firmware Type window appears Click OK...

Page 111: ...and settings clearly defined for LAN A and or B Step 3 6 assumes that the reader is familiar with the complete ConfigPro LAN settings configuration steps and that these steps have already been consid...

Page 112: ...t menu CommandSSH allows remote access to the command prompt D20M prompt These are both TCP connections 4 Click OK when the D20MX device properties are set Result The applications present in the SAN f...

Page 113: ...X factory default configuration as a reference 5 3 2 Double click on this factory default configuration and click the System Point Database Applications tab 5 3 3 Double click on the Wesmaint II appli...

Page 114: ...on Right click on the RADIUS Role Table B014RADR and import the B014RADR settings previously exported Select the B014RADR CSV file and click Select 5 4 Configure the IP Redundancy Monitor B152 applica...

Page 115: ...s tab 5 4 3 Double click the System Point Database Applications Table Select the IP Redundancy Monitor from the list of application and click Descriptors Right click the Export icon and export the des...

Page 116: ...click the device Navigate to the System point database Applications tab Double click the System Point Database application Select the IP Redundancy Monitor from the list of applications Click Descrip...

Page 117: ...configure all other enabled applications based on their respective configuration guides This is required before a configuration can be successfully generated without errors 5 4 10 Right click the devi...

Page 118: ...If not repeat the export import process 6 Generate the device configuration after a configuration has been properly configured Result If there are no errors or warnings the red dot on the device shou...

Page 119: ...of configuration can be done by either Option 1 use ConfigPro terminal emulator and the F7 key on page 119 Option 2 Use a non ConfigPro terminal emulator and a dl command on page 122 Option 1 use Conf...

Page 120: ...select Device Communications Communications Options Result The Communications Options window appears 2 2 Set the communication options Baud Rate 19200 Parity None Data Bits 8 Stop Bits 1 2 3 Connect t...

Page 121: ...MX baud rate changes from 19200 to 115200 2 5 3 Disconnect the D20MX from ConfigPro by selecting Communications Disconnect 2 5 4 Open the communication properties by selecting Device Communications Co...

Page 122: ...ator to the D20MX RTU using the dl command this is similar to the download process of a D20ME firmware configuration This download process is done at the D20M prompt To download a configuration to the...

Page 123: ...he factory default configuration for the D20MX comes with one default user account with Username admin Password changeme 4 Navigate to the D20M prompt this is called a SHELL prompt an equivalent of th...

Page 124: ...XDEVICE SHX file located in the project directory below can simply be dragged and dropped in the Tera term window 8 Locate the D20MXDEVICE SHX file 8 1 Open Windows explorer 8 2 Navigate to the projec...

Page 125: ...guration If you synchronize a configuration with any of the following errors there are no usernames configured in the B014 User table the B014 User table is disabled or the B014 application definition...

Page 126: ...nfiguration port 22 has been created in the Services section of the Device LAN Properties 5 If the following window appears click Yes 6 Make a copy of the generated configuration file D20MXDEVICE SHX...

Page 127: ...D20M prompt of the D20MX RTU this is the SHELL option 3 menu 10 Suspend the processor by typing sp and pressing Enter 11 Copy the configuration by typing cc and pressing Enter 12 Select the configurat...

Page 128: ...ed by ConfigPro 1 Press the Windows Key and E at the same time Result The Windows Explorer window appears 2 Navigate to a folder to which you have write permissions Result The content of the folder is...

Page 129: ...esult Windows Explorer window showing the new D20MXV1 20 folder is displaying the files shown in the above table Installing application definitions archived To install the application definitions 1 Fr...

Page 130: ...urce directory Go to the D20MX Documentation CD folder Configuration Files sub folder Application Definitions folder 3 2 Select the D20MXv1_2Appldefs file 3 3 Click Select 4 Click Next Result The Conf...

Page 131: ...APPENDIX D USING CONFIGPRO WITH D20MX D20MX HARDWARE USER S MANUAL GE INFORMATION 131 6 Click Next Result The ConfigPro Application Installer Installation Complete window appears 7 Click Finish...

Page 132: ...folder contains the APPLDEF sub folder with all the application definition files To install missing application definition files 1 From ConfigPro select Tools Application Installer Result The ConfigPr...

Page 133: ...33 3 Click Next Result The ConfigPro Application Installer Select Source Directory window appears 4 Select a Source director this is the DEFNs APPLDEF path within the D20MX Documentation CD 5 Select t...

Page 134: ...D20MX 6 Click Next Result The ConfigPro Application Installer Select a ConfigPro Project window appears 7 Select the ConfigPro project that requires these application definitions 8 Click Next Result...

Page 135: ...o which the application definitions are to be copied To determine the destination directory in ConfigPro go to File Preferences Directories This is the path highlighted in the screen capture below C W...

Page 136: ...136 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX D USING CONFIGPRO WITH D20MX...

Page 137: ...uge unit of measure bps bits per second unit of measure CCU Central Control Unit CE Mark Mandatory conformity mark for products placed on the market in the European Economic Area EEA CISPR Special int...

Page 138: ...time code format kbps kilo bits per second unit of measure LAN Local Area Network lb pound unit of measure for weight LED Light Emitting Diode LLA Loss Link Alert LRU Logical Remote Unit Mb Mega bits...

Page 139: ...s SQL Structured Query Language SRU Sub Remote Unit TIA Telecommunication Industries Association Tx Transmit TXD Transmit Data UART Universal Asynchronous Receiver Transmitter UTC Universal Time Coord...

Page 140: ...140 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX E LIST OF ACRONYMS...

Page 141: ...date D20 D200 78 CONNECT THE POWER SUPPLY 38 CUSTOMER SUPPORT 11 D D 20 LINK CABLING 43 D20 chassis overview 19 modems 23 peripherals 23 power supplies 22 system redundancy 49 D20 CHASSIS LAYOUTS 31 D...

Page 142: ...S 85 OVERVIEW cabling 41 D20 chassis 19 D20MX processor 16 product 15 P PACKAGE CONTENTS 38 PERIODIC INSPECTION 87 PERIPHERALS 23 PHYSICAL SPECIFICATIONS 28 PORT RS 232 49 POWER SUPPLIES 22 POWER UP 5...

Page 143: ...r 11 technical 11 SWITCH OVER check 59 verify hardware or software 60 SYSTEM redundancy 49 specifications 27 T TECHNICAL SUPPORT 11 TERA TERM SET UP 64 TERMINAL emulation 56 WESMAINT II 56 57 TERMINAL...

Page 144: ...144 GENERAL D20MX HARDWARE USER S MANUAL INDEX...

Page 145: ...nfigurations to the D20MX and Updating D20 D200 Configurations to use the D20MX firmware definition with ConfigPro Added an Appendix for Resetting a read write user password 3 January 11 2013 R Rees U...

Page 146: ...146 GE INFORMATION D20MX HARDWARE USER S MANUAL...

Reviews: