Table 3 provides the License Group legend.
Table 3: D20MX license group
NOTE
The license group is an option in the D20MX order code. Refer to Table 10 and Table 11 for
details. Ordering a D20MX with a particular license group option enables all applications in
that group to run on the D20MX.
Table 4 lists the embedded images included in the D20MX firmware.
B015
Bridgeman
Allows applications to communicate with other peer
applications. Automatically routing messages to the
destination application. Intended to work within layered
software architectures. Provides the routing functions of a
network layer, but does not add a network layer header to
outgoing messages.
530
B023
DNP V3.00 DCA
The Distributed Network Protocol V3.00 DCA acts as the
master to one or more remote devices using the DNP V3.00
protocol.
755
Yes
B034-0N
Redundant Monitor for
D20MX
Monitors CCU states and initiates failover. Also, receives
command requests to perform database synchronization,
switchover and failover.
300
Yes
B045-0
D20AC WESMAINT II+
Display Screens
Provides D20AC WESMAINT II+ displays.
101
B052-0N
DNP Internet Data Link for
D20MX
DNP V3.00 data link over internet.
351
B058-0
IEC 870-5 Data Link
FT 1.2 primary data link configuration
231
New
B060-0
IEC 870-5-101 DCA
Acts as a master (primary) communication device, initiating
data exchanges. It is capable of sending control commands
to the remote devices, and processing data autonomously
collected by the data link layer.
210
New
B071-0
WESMAINT File Upload
Uploads files via the WESMAINT port as S records or using
ZMODEM.
200
B085
IEC Balanced Data Link
Provides services to send and receive messages using the
IEC 60870-5 FT 1.2 Balanced Protocol over point-to-point
links, with support for a dial-up modem. Works with one
user in point-to-point configurations, or multiple users in
dial-up configurations.
130
New
B086-0
IEC 60870-5-104 Data Link Provides a service to reliably transfer IEC 60870-5-101
Application Service Data Units (ASDU) over a TCP/IP network.
Implements this service using the transport layer interface
protocol IEC 60870-5-104.
131
New
B100-0
Internet Protocol Stack
Configuration of the LAN
141
B152-1N
IP Redundancy Monitor
DTA for D20MX
Provides health and active pseudo DI points for LAN Ports.
200
Yes
SAN0001 Application Definitions
B009
Mailbox DTA
System point conversion application.
401
B021N
DNP V3.00 DPA for D20MX The Distributed Network Protocol (DNP) DPA enables master
stations to retrieve and modify local data using the DNP
V3.00 Application Layer Protocol.
990
Yes
SAN0002 Application Definitions
B009
Mailbox DTA
System point conversion application.
310
B021N
DNP V3.00 DPA for D20MX The Distributed Network Protocol (DNP) DPA enables master
stations to retrieve and modify local data using the DNP
V3.00 Application Layer Protocol.
913
Yes
License
Group
D20MX
Application
ID
Application Name
Description
Application
Definition
Version
Changed
LIcense Group
Group Description
001
D2X Classic Applications
Summary of Contents for D20MX
Page 6: ...6 GENERAL D20MX HARDWARE USER S MANUAL TABLE OF CONTENTS...
Page 10: ...10 GE INFORMATION D20MX HARDWARE USER S MANUAL ABOUT THIS DOCUMENT...
Page 30: ...30 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 1 BEFORE YOU START...
Page 40: ...40 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 2 INSTALLING THE D20MX...
Page 54: ...54 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 3 CONNECTING TO DEVICES AND NETWORKS...
Page 100: ...100 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX B STANDARDS PROTECTION...
Page 136: ...136 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX D USING CONFIGPRO WITH D20MX...
Page 140: ...140 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX E LIST OF ACRONYMS...
Page 144: ...144 GENERAL D20MX HARDWARE USER S MANUAL INDEX...
Page 146: ...146 GE INFORMATION D20MX HARDWARE USER S MANUAL...