GE Multilin
B30 Bus Differential System
B-61
APPENDIX B
B.4 MEMORY MAPPING
B
C891
Direct Input 1 Number
0 to 96
---
1
F001
0
C892
Direct Input 1 Default State
0 to 3
---
1
F086
0 (Off)
C893
Direct Input 1 Events
0 to 1
---
1
F102
0 (Disabled)
C894
...Repeated for Direct Input 2
C898
...Repeated for Direct Input 3
C89C
...Repeated for Direct Input 4
C8A0
...Repeated for Direct Input 5
C8A4
...Repeated for Direct Input 6
C8A8
...Repeated for Direct Input 7
C8AC
...Repeated for Direct Input 8
C8B0
...Repeated for Direct Input 9
C8B4
...Repeated for Direct Input 10
C8B8
...Repeated for Direct Input 11
C8BC
...Repeated for Direct Input 12
C8C0
...Repeated for Direct Input 13
C8C4
...Repeated for Direct Input 14
C8C8
...Repeated for Direct Input 15
C8CC
...Repeated for Direct Input 16
C8D0
...Repeated for Direct Input 17
C8D4
...Repeated for Direct Input 18
C8D8
...Repeated for Direct Input 19
C8DC
...Repeated for Direct Input 20
C8E0
...Repeated for Direct Input 21
C8E4
...Repeated for Direct Input 22
C8E8
...Repeated for Direct Input 23
C8EC
...Repeated for Direct Input 24
C8F0
...Repeated for Direct Input 25
C8F4
...Repeated for Direct Input 26
C8F8
...Repeated for Direct Input 27
C8FC
...Repeated for Direct Input 28
C900
...Repeated for Direct Input 29
C904
...Repeated for Direct Input 30
C908
...Repeated for Direct Input 31
C90C
...Repeated for Direct Input 32
Direct Input/Output Alarms (Read/Write Setting)
CAD0
Direct Input/Output Channel 1 CRC Alarm Function 0 to 1
---
1
F102
0 (Disabled)
CAD1
Direct Input/Output Channel 1 CRC Alarm
Message Count
100 to 10000
---
1
F001
600
CAD2
Direct Input/Output Channel 1 CRC Alarm
Threshold
1 to 1000
---
1
F001
10
CAD3
Direct Input/Output Channel 1 CRC Alarm Events
0 to 1
---
1
F102
0 (Disabled)
CAD4
Reserved (4 items)
1 to 1000
---
1
F001
10
CAD8
Direct Input/Output Channel 2 CRC Alarm Function 0 to 1
---
1
F102
0 (Disabled)
CAD9
Direct Input/Output Channel 2 CRC Alarm
Message Count
100 to 10000
---
1
F001
600
CADA
Direct Input/Output Channel 2 CRC Alarm
Threshold
1 to 1000
---
1
F001
10
CADB
Direct Input/Output Channel 2 CRC Alarm Events
0 to 1
---
1
F102
0 (Disabled)
CADC
Reserved (4 items)
1 to 1000
---
1
F001
10
CAE0
Direct Input/Output Ch 1 Unreturned Messages
Alarm Function
0 to 1
---
1
F102
0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 53 of 60)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for B30 UR Series
Page 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...