5-42
B30 Bus Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
REPORT CONTROL CONFIGURATION
CONFIGURABLE REPORT 1
REPORT 1 DATASET ITEMS
To create the dataset for logical node LN, program the
ITEM 1
to
ITEM 64
settings to a value from the list of IEC 61850 data
attributes supported by the B30. Changes to the dataset will only take effect when the B30 is restarted. It is recommended
to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1,
GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
XCBR CONFIGURATION
The
CLEAR XCBR1 OpCnt
setting represents the breaker operating counter. As breakers operate by opening and closing, the
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1.
REPORT 1
DATASET ITEMS
ITEM 1:
Range: all valid MMS data item references
MESSAGE
ITEM 2:
Range: as shown above
MESSAGE
ITEM 3:
Range: as shown above
↓
MESSAGE
ITEM 64:
Range: as shown above
XCBR
CONFIGURATION
XCBR1 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XCBR2 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XCBR3 ST.LOC OPERAND
Off
Range: FlexLogic operand
↓
MESSAGE
XCBR6 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
CLEAR XCBR1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XCBR2 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XCBR3 OpCnt:
No
Range: No, Yes
↓
MESSAGE
CLEAR XCBR6 OpCnt:
No
Range: No, Yes
Summary of Contents for B30 UR Series
Page 10: ...x B30 Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 122: ...4 30 B30 Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 326: ...5 204 B30 Bus Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 412: ...A 12 B30 Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 554: ...D 10 B30 Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 566: ...E 12 B30 Bus Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 574: ...F 8 B30 Bus Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...