In case of the following protection or failures, the indoor unit shall display corresponding codes, which
are explained as follows:
Code Explanation
E1
Compressor High-pressure Protection
E2
Indoor Antifreeze Protection
E3
Compressor Low-pressure Protection
E4
Exhaust Pipe High-temp. Protection
E5
Low-voltage Protection
Fan of indoor unit touches other
positions
Adjust fan position
Foreign articles inside the indoor unit
Remove foreign articles
Vibration of compressor is violent
Adjust support foot mat of
compressor, tighten loose bolts
Abnormal sound
and vibration
Pipes of outdoor unit bump together
Separate bumping pipes
Metal plates bump together inside the
unit
1. Tighten connection screws
2. Attach vibration damping gum
between metal plates
Indoor fan bumps cabinet
Adjust fan position
Abnormal sound from inside
compressor
Replace Compressor
Abnormal electromagnetic noise from
4-way valve when in heating operation
Internal short circuit of solenoid
valve, replace solenoid valve
Water leakage
Block or breakage of drainage pipe
Replace drainage pipe
The refrigerant pipe joint is not
wrapped firmly
Wrap and bind it again firmly
Summary of Contents for AIR F24
Page 2: ... 2 ...
Page 3: ... 3 ...
Page 5: ... 5 M Mo od de el l R Re em ma ar rk ks s GE AIR F34 3PH 400V 50Hz R407C ...
Page 6: ... 6 M Mo od de el l R Re em ma ar rk ks s GE AIR F41 3PH 400V 50Hz R407C ...
Page 12: ... 12 Applicable to GE AIR F34 IN GE AIR F41 IN ...
Page 14: ... 14 Applicable to GE AIR F41 OUT Unit mm Bolt Nut Wrench ...
Page 16: ... 16 GE AIR F24 GE AIR F34 6 6 E El le ec ct tr ri ic ca al l D Di ia ag gr ra am m ...