![background image](http://html.mh-extra.com/html/ge/air-f24/air-f24_service-manual_122416039.webp)
-
39
-
Operating Procedures / Photos
Disassemble Capillary
Unsold the soldering points at the capillary,
the valve and the condenser to remove the
capillary. Pay attention not to allow the
soldering slag to block the capillary.
(Fig 8-59)
Capillary
Disassemble Valve
Unscrew the two screws fixing the gas valve,
unsolder the soldering point between the gas
valve and the return-air duct and remove the
gas valve (note: when unsoldering the
soldering point, use wet cloth to completely
wrap the gas valve to prevent valve body from
being harmed by high temperature).
Unscrew the two screws fixing the liquid valve,
unsolder the soldering point connecting the
liquid valve and the fork type pipe, and remove
the liquid valve.
(Fig 8-60)
Liquid Valve Screw Gas Valve
Disassemble Compressor
Firstly unsolder the pipes connecting the
compressor, and then unscrew the three foot
nuts at the compressor to remove the
compressor. (Fig 8-61)
Foot Nut
Summary of Contents for AIR F24
Page 2: ... 2 ...
Page 3: ... 3 ...
Page 5: ... 5 M Mo od de el l R Re em ma ar rk ks s GE AIR F34 3PH 400V 50Hz R407C ...
Page 6: ... 6 M Mo od de el l R Re em ma ar rk ks s GE AIR F41 3PH 400V 50Hz R407C ...
Page 12: ... 12 Applicable to GE AIR F34 IN GE AIR F41 IN ...
Page 14: ... 14 Applicable to GE AIR F41 OUT Unit mm Bolt Nut Wrench ...
Page 16: ... 16 GE AIR F24 GE AIR F34 6 6 E El le ec ct tr ri ic ca al l D Di ia ag gr ra am m ...