P50 Agile P153
12 Maintenance and Troubleshooting
P153/EN M/B
12-9
3
TROUBLESHOOTING
The relay continuously monitors the hardware and detects any hardware fault/error. In case of
hardware failure relay displays the corresponding error code on the LCD.
•
The IED performs continuous periodic self-diagnostic procedure at every one minute for
checking of all errors excluding Setting Error.
•
If the error is cleared during self-diagnostic procedure, corresponding error bit will be cleared.
•
For Setting Error, ADC Error and FRAM1 Error, IED goes in
OUT OF SERVICE
mode
(Protection will be blocked). The
OUT OF SERVICE
LED on the front facia will continuously
blink at 1 sec interval and
ON
LED indication will turn from GREEN to RED.
The faults errors are stored in the ‘Main’t Rec Num= “and can be viewed from
Maint Record
submenu. The Error code is stored in 16 bit integer.
The bit definition applicable to P153 is shown as below:
Bit 12 -
15
Bit 11
Bit 10
Bit 6-9
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Unused
Incompatible
Firmware
Incompatible
CommFirmware
Unused FRAM 1
Error
ADC
Error
Unused
RTC
Error
Unused
Setting
Error
The Error code descriptions are given below:
Sr. No
Error Code
display
Error Data
Bitwise
Description
Cause
Action taken
by MCU
Proposed action
1
0001
0000 0000
0000 0001
SETTING
Error
1.
Setting corrupted
2.
Change of Setting
address in memory
ON LED turns Red
and OUT OF
SERVICE LED
starts blinking.
(Protection is
blocked)
Go to
CONFIGURATION
menu, restore default
settings and then save
settings. Press (EDIT +
CLEAR).
2
0004
0000 0000
0000 0100
RTC
Error
1.
I2C Bus Error
2.
Damaged RTC
3.
Battery backup not
functioning
ON LED turns Red
Set correct values for
Date & Time and press
(EDIT + CLEAR).
3
0010
0000 0000
0001 0000
ADC
Error
1.
ADC device not
working.
2.
SPI bus error
ON LED turns Red
and OUT OF
SERVICE LED
starts blinking.
(Protection is
blocked)
Press (EDIT
+
CLEAR)
4
0020
0000 0000
0010 0000
FRAM 1
Error
1.
SPI bus error
2.
FRAM not working
ON LED turns Red Press (EDIT + CLEAR)
5
Incompatible
CommFirmware
0000 0100
0000 0000
Incompatible
CommFirmware
Error
Firmware being flashed
has communication
protocol not compatible to
the protocol option as per
relay model number.
ON LED turns Red
Flash correct FW as per
the cortec information
on the relay.
6
Incompatible
Firmware
0000 1000
0000 0000
Incompatible
Firmware
Error
Firmware being flashed
is not compatible to the
hardware as per relay
model number. (e.g.
mismatch in CT selection/
DI Input threshold voltage
etc.)
ON LED turns Red
and OUT OF
SERVICE LED
starts blinking.
(Protection is
blocked)
Flash correct FW as per
the cortec information
on the relay.
Summary of Contents for Agile P50 Series
Page 3: ...P50 Agile P153 1 Introduction P153 EN M B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P153 1 2 P153 EN M B...
Page 10: ...1 Introduction P50 Agile P153 1 8 P153 EN M B...
Page 11: ...P50 Agile P153 2 Safety Information P153 EN M A 2 1 SAFETY INFORMATION CHAPTER 2...
Page 22: ...Chapter 2 Safety Information P50 Agile P153 2 12 P153 EN M A...
Page 23: ...P50 Agile P153 3 Hardware Design P153 EN M B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 24: ...3 Hardware Design P50 Agile P153 3 2 P153 EN M B...
Page 32: ...3 Hardware Design P50 Agile P153 3 10 P153 EN M B...
Page 33: ...P50 Agile P153 4 Front Panel P153 EN M B 4 1 FRONT PANEL CHAPTER 4...
Page 34: ...4 Front Panel P50 Agile P153 4 2 P153 EN M B...
Page 39: ...P50 Agile P153 5 Configuration P153 EN M B 5 1 CONFIGURATION CHAPTER 5...
Page 40: ...P50 Agile P153 5 Configuration P153 EN M B 5 2...
Page 150: ...P50 Agile P153 5 Configuration P153 EN M B 5 112...
Page 151: ...P50 Agile P153 6 Protection Functions P153 EN M B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 152: ...6 Protection Functions P50 Agile P153 6 2 P153 EN M B...
Page 168: ...7 Protection Parameter Settings P50 Agile P153 7 2 P153 EN M B...
Page 189: ...P50 Agile P153 8 Monitoring Control P153 EN M B 8 1 MONITORING CONTROL CHAPTER 8...
Page 190: ...8 Monitoring Control P50 Agile P153 8 2 P153 EN M B...
Page 207: ...P50 Agile P153 9 SCADA Communications P153 EN M B 9 1 SCADA COMMUNICATIONS CHAPTER 9...
Page 208: ...12 SCADA Communications P50 Agile P153 9 2 P153 EN M B...
Page 220: ...12 SCADA Communications P50 Agile P153 9 14 P153 EN M B...
Page 221: ...P50 Agile P153 10 Installation P153 EN M B 10 1 INSTALLATION CHAPTER 10...
Page 222: ...10 Installation P50 Agile P153 10 2 P153 EN M B...
Page 234: ...13 Commissioning Instructions P50 Agile P153 13 2 P153 EN M B...
Page 242: ...12 Maintenance and Troubleshooting P50 Agile P153 12 2 P153 EN M B...
Page 250: ...12 Maintenance and Troubleshooting P50 Agile P153 12 10 P153 EN M B...
Page 252: ...13 Technical Specifications P50 Agile P153 13 2 P153 EN M B...
Page 263: ...P50 Agile P153 14 Wiring Diagrams P153 EN M B 14 1 WIRING DIAGRAMS CHAPTER 14...
Page 264: ...14 Wiring Diagrams P50 Agile P153 14 2 P153 EN M B...
Page 267: ......