Cables
GFK-0356Q
Chapter 10 Cables
10-51
10
Table 10-9. Wire List for 24-Pin Connectors
Pin
Number
Pair #
Wire Color Code
Pin Number
Pair #
Wire Color Code
A1
1
BROWN
B1
7
VIOLET
A2
1
BROWN/BLACK
B2
7
VIOLET/BLACK
A3
2
RED
B3
8
WHITE
A4
2
RED/BLACK
B4
8
WHITE/BLACK
A5
3
ORANGE
B5
9
GRAY
A6
3
ORANGE/BLACK
B6
9
GRAY/BLACK
A7
4
YELLOW
B7
10
PINK
A8
4
YELLOW/BLACK
B8
10
PINK/BLACK
A9
5
DARK GREEN
B9
11
LIGHT BLUE
A10
5
DARK GREEN/BLACK
B10
11
LIGHT BLUE/BLACK
A11
6
DARK BLUE
B11
12
LIGHT GREEN
A12
6
DARK BLUE/BLACK
B12
12
LIGHT GREEN/BLACK
CONNECTOR
3 2 1
12
12
3 2 1
B ROW
A ROW
NOTE
Each wire pair has a solid color wire and that same color
wire with a black tracer. For example, Pair 1 has a solid
brown wire paired with a brown wire with a black tracer.
Replacement/Obsolescence Information
Cable IC693CBL315 (now obsolete also) replaced cable IC693CBL310 when that cable
became obsolete. The only difference between these two cables is in the wire color coding.
When cable IC693CBL315 became obsolete, the replacement for these cables became
IC693CBL327 and IC693CBL328. Cables IC693CBL310/315 have straight connectors.
Cables IC693CBL327/328 have right angle connectors. The right angle connectors require
less depth in front of the PLC, so allow the use of a smaller enclosure in some applications.
Connector Depth for IC693CBL315
The following illustration shows the space required in front of the PLC when this cable is
connected to a module. The depth of the cabinet that the PLC is mounted in should allow for the
depth added by this connector.