Cables
GFK-0356Q
Chapter 10 Cables
10-43
10
Table 10-4. Wire List for 24-Pin Connectors
Pin Number
Pair #
Wire Color Code
Pin Number
Pair #
Wire Color Code
A1
1
BLACK
B1
7
BLUE
A2
1
W
HITE
B2
7
W
HITE
A3
2
BROWN
B3
8
VIOLET
A4
2
WHITE
B4
8
WHITE
A5
3
RED
B5
9
GRAY
A6
3
W
HITE
B6
9
W
HITE
A7
4
ORANGE
B7
10
BROWN
A8
4
WHITE
B8
10
BLACK
A9
5
YELLOWB9
11
RED
A10
5
WHITE
B10
11
BLACK
A11
6
GREEN
B11
12
ORANGE
A12
6
WHITE
B12
12
BLACK
CONNECTOR
3 2 1
12
12
3 2 1
B ROW
A ROW
NOTE
Each pair of wires should be tied together with heat
h i k
t
ubing for identification purposes. For example, a
h t
piece of heat shrink tubing should be placed around the
BLACK and WHITE wire pair (Pair #1) that connect to
Pins A1 and A2, etc.
Replacement/Obsolescence Information
This cable became obsolete and was replaced by cable IC693CBL315 (now obsolete also).
The only difference between these two cables is in the wire color coding.
When cable IC693CBL315 became obsolete, the replacement for these cables became
IC693CBL327 and IC693CBL328. Cables IC693CBL310/315 have straight connectors.
Cables IC693CBL327/328 have right angle connectors. The right angle connectors require
less depth in front of the PLC, so allow the use of a smaller enclosure in some applications.
Data sheets for cables IC693CBL315 and IC693CBL327/328 can be found in this chapter.
Connector Depth for Cable IC693CBL310
The following illustration shows the space required in front of the PLC when this cable is
connected to a module. The depth of the cabinet that the PLC is mounted in should allow for the
depth added by this connector.