5-157
5 SETTINGS
5.7 CONTROL ELEMENTS
5
b) SPECIAL APPLICATION OF THE SYNCHROCHECK ELEMENT
The synchrocheck element is intended for applications where the potential sources are located on either side of the breaker
to be closed. It can also be used in cases where a power transformer is located between the two potential sources by com-
pensating for the power transformer phase shift with the auxiliary VT connection to the C60 and the auxiliary VT connection
setting, as shown in the following example.
Figure 5–76: SYNCHROCHECK APPLIED ACROSS A TRANSFORMER
In this example, the phase voltage VT input is programmed as “Delta” with a secondary setting of 120 volts and a ratio of
13800 V/ 120 V = 115. The auxiliary VT connection is selected to be VAB since this vector is in phase with VA on the trans-
former primary. The secondary setting is 69 volts and the auxiliary VT ratio is calculated as 13800 V / 69 V = 200. Note that
the metered values for the auxiliary VT will now reflect the AB voltage of the secondary side of the transformer.
Phase VT input
A
B
C
a
b
c
System nominal
Vpp = 13.8 kV
System nominal
Vpp = 230 kV
138000 : 69
14400 : 120
~5a
52
~5c ~6a ~6c ~7a ~7c
~8a
~8c
Auxiliary VT input
UR-series device
843808A1.CDR
210000
14000
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...