B-26
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5744
...Repeated for RTD Input 45
5757
...Repeated for RTD Input 46
576A
...Repeated for RTD Input 47
577D
...Repeated for RTD Input 48
Flexlogic Timers (Read/Write Setting) (32 modules)
5800
FlexLogic™ Timer 1 Type
0 to 2
---
1
F129
0 (millisecond)
5801
FlexLogic™ Timer 1 Pickup Delay
0 to 60000
---
1
F001
0
5802
FlexLogic™ Timer 1 Dropout Delay
0 to 60000
---
1
F001
0
5803
Reserved (5 items)
0 to 65535
---
1
F001
0
5808
...Repeated for FlexLogic™ Timer 2
5810
...Repeated for FlexLogic™ Timer 3
5818
...Repeated for FlexLogic™ Timer 4
5820
...Repeated for FlexLogic™ Timer 5
5828
...Repeated for FlexLogic™ Timer 6
5830
...Repeated for FlexLogic™ Timer 7
5838
...Repeated for FlexLogic™ Timer 8
5840
...Repeated for FlexLogic™ Timer 9
5848
...Repeated for FlexLogic™ Timer 10
5850
...Repeated for FlexLogic™ Timer 11
5858
...Repeated for FlexLogic™ Timer 12
5860
...Repeated for FlexLogic™ Timer 13
5868
...Repeated for FlexLogic™ Timer 14
5870
...Repeated for FlexLogic™ Timer 15
5878
...Repeated for FlexLogic™ Timer 16
5880
...Repeated for FlexLogic™ Timer 17
5888
...Repeated for FlexLogic™ Timer 18
5890
...Repeated for FlexLogic™ Timer 19
5898
...Repeated for FlexLogic™ Timer 20
58A0
...Repeated for FlexLogic™ Timer 21
58A8
...Repeated for FlexLogic™ Timer 22
58B0
...Repeated for FlexLogic™ Timer 23
58B8
...Repeated for FlexLogic™ Timer 24
58C0
...Repeated for FlexLogic™ Timer 25
58C8
...Repeated for FlexLogic™ Timer 26
58D0
...Repeated for FlexLogic™ Timer 27
58D8
...Repeated for FlexLogic™ Timer 28
58E0
...Repeated for FlexLogic™ Timer 29
58E8
...Repeated for FlexLogic™ Timer 30
58F0
...Repeated for FlexLogic™ Timer 31
58F8
...Repeated for FlexLogic™ Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5900
Phase Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5901
Phase Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5902
Phase Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5903
Phase Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5904
Phase Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5905
Phase Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5906
Phase Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5907
Phase Time Overcurrent 1 Voltage Restraint
0 to 1
---
1
F102
0 (Disabled)
5908
Phase TOC 1 Block For Each Phase (3 items)
0 to 65535
---
1
F300
0
590B
Phase Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
590C
Phase Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
590D
Reserved (3 items)
0 to 1
---
1
F001
0
5910
...Repeated for Phase Time Overcurrent 2
Table B–9: MODBUS MEMORY MAP (Sheet 19 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...