5-16
C60 Breaker Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
b) SERIAL PORTS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
Ö
SERIAL PORTS
The C60 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for
local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet
or RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that
these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of
these ports may be connected to a computer running EnerVista UR Setup. This software can download and upload setting
files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and con-
nected to a DCS, PLC or PC using the RS485 ports.
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
each transmission.
c) NETWORK
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
NETWORK
These messages appear only if the C60 is ordered with an Ethernet card.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The
NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a set-
ting for the TCP/UDP port number. These settings are used only in advanced network configurations and should normally
be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays
behind a router). By setting a different
TCP/UDP PORT NUMBER
for a given protocol on each UR-series relay, the router can
map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured
to use the correct port number if these settings are used.
When the NSAP address, any TCP/UDP port number, or any user map setting (when used with DNP) is changed, it
will not become active until power to the relay has been cycled (off-on).
SERIAL PORTS
RS485 COM1 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
MESSAGE
RS485 COM1 PARITY:
None
Range: None, Odd, Even
Only active if CPU Type E is ordered
MESSAGE
RS485 COM1 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10
Only active if CPU Type E is ordered
MESSAGE
RS485 COM2 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
MESSAGE
RS485 COM2 PARITY:
None
Range: None, Odd, Even
MESSAGE
RS485 COM2 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10
NETWORK
IP ADDRESS:
0.0.0.0
Range: Standard IP address format
Not shown if CPU Type E is ordered.
MESSAGE
SUBNET IP MASK:
0.0.0.0
Range: Standard IP address format
Not shown if CPU Type E is ordered.
MESSAGE
GATEWAY IP ADDRESS:
0.0.0.0
Range: Standard IP address format
Not shown if CPU Type E is ordered.
MESSAGE
OSI NETWORK
ADDRESS (NSAP)
Range: Select to enter the
OSI NETWORK ADDRESS
.
Not shown if CPU Type E is ordered.
MESSAGE
ETHERNET OPERATION
MODE: Full-Duplex
Range: Half-Duplex, Full-Duplex
Not shown if CPU Type E or N is ordered.
NOTE
NOTE
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...