Figure 5–73: ACKNOWLEDGE MODE
Application example
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group shall be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group shall be applied automatically after 5 seconds of inactivity of
the control inputs. When the relay powers up, it should synchronize the setting group to the three-bit control input.
Make the following changes to setting group control in the
SETTINGS
ÖØ
CONTROL ELEMENTS
Ö
SETTING GROUPS
menu:
SETTING GROUPS FUNCTION:
“Enabled”
GROUP 4 ACTIVATE ON:
“SELECTOR 1 POS 4"
SETTING GROUPS BLK:
“Off”
GROUP 5 ACTIVATE ON:
“Off”
GROUP 2 ACTIVATE ON:
“SELECTOR 1 POS 2"
GROUP 6 ACTIVATE ON:
“Off”
GROUP 3 ACTIVATE ON:
“SELECTOR 1 POS 3"
Make the following changes to selector switch element in the
SETTINGS
ÖØ
CONTROL ELEMENTS
ÖØ
SELECTOR SWITCH
Ö
SELECTOR SWITCH 1
menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:
842736A1.CDR
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
POS 7
BIT 0
BIT 1
BIT 2
pre-existing
position 2
changed to 4 with
a pushbutton
changed to 1 with
a 3-bit input
changed to 2 with
a pushbutton
STP ALARM
BIT ALARM
ALARM
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...