Programming instructions
QS4 Technical Reference Manual
4.19
What is it you want to do
This is how you do it
Change the personality code for a circuit on a
SIGA module
Note:
The personality codes shown in the pick lists
vary depending on the SIGA module and the
chosen device type.
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Module > Edit > Enter Serial #
and then scan or enter the serial number of the
module.
3. For a single-address module or the first
address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address
module, choose Device 2.
4. Choose Personality, select a personality code
from the pick list, and then press Enter.
5. Choose Exit.
Enable the loop controller mapping function
AutoLearn default:
Mapping disabled
1. Press Menu.
2. Log onto the panel as a Level 4 operator.
3. Choose Enable > Loop Mapping.
4. Enter the card number of the SLIC that
connects to the device you want to replace.
Wait until mapping finishes before continuing.
5. Choose Cards > Edit.
6. Enter the card number of the SLIC that
connects to the device you want to replace.
7. Choose Accept Map.
If actual and expected data for detectors and
modules are the same, press Enter.
8. Choose Exit > Exit > Save.
Technical Manuals Online! - http://www.tech-man.com