Programming instructions
QS4 Technical Reference Manual
4.9
Table 4-2: AutoLearn initial project settings
Option
Value
Description
Edit?
Alarm Silence
Audible only
Turns off Audible and Common Alarm Output circuits
when someone presses Alarm Silence.
CU
Drill
Audible only
Turns off Audible and Common Alarm Output circuits
when someone presses Drill.
CU
Drill Activation Type
Steady
The Drill signal is a constant signal.
CU
Alarm Signal
Silence/Reset Inhibit
None
Alarm Silence or Reset functions are not inhibited. You
can turn off (silence) notification circuits or reset the
panel any time after notification circuits are activated.
FPP/CU
Buzzer Reminder Time
Indefinitely
The panel trouble buzzer remains silenced until the
control panel processes a new off-normal signal.
No
AC Power Trouble
Delay
6 h
The panel will operate on battery power for 6 hours
before signaling a trouble condition.
FPP/CU
Two-stage Timer
0 s (UL)
300 s (ULC)
The panel will turn on notification circuits immediately
after processing an alarm signal (UL) or after 5 minutes
(ULC).
CU
Zone Resound Inhibit
No
Turn silenced NAC circuits back on if an active alarm
input circuit remains in the active condition after
resetting the panel.
No
Primary Routing
All Cabinets
Distribute event records to all panels in the system
when primary routing is activated.
CU
Alternate Routing
All Cabinets
Distribute event records to all panels in the system
when alternate routing is activated.
CU
Language
English (U.S.)
U.S. English displayed on CPU/Display.
No
Relay 1 Type
Alarm
Alarm events cause the contact positions of Relay 1 on
the PS6 to change positions.
No
Relay 2 Type
Supervisory
Supervisory events cause the contact positions of Relay
2 on the PS6 to change positions.
No
Relay 3 Type
Trouble
Trouble events cause the contact positions of Relay 3
on the PS6 to change positions.
No
Relay 4 Type
Monitor
Monitor events cause the contact positions of Relay 4
on the PS6 to change positions.
CU