Standard applications
5.10
QS4 Technical Reference Manual
Remote station protective signaling system
1
2
3
1. FACP:
Fire alarm control panel with a CPU,
PS6, ZB16–4, and standby batteries.
2. MFC–A Accessory Enclosure:
Used for
mounting the remote fire alarm equipment.
3. RPM Reverse Polarity Module:
Provides three
independent reverse polarity signals (alarm,
supervisory, trouble) for transmitting system status
to a remote location.
Notes
• Place the MFC–A and the FACP in the same
room and connect using a section of conduit no
greater than 20 ft in length. Run all wiring
between cabinets through the conduit.
• Set JP2 on the PS6 for ACC PWR.
• Install a 3.9 K
Ω
EOLR across TB1–1 and TB1–
2 on the RPM.
Figure 5-4: Typical equipment layout, Remote station protective signaling application