Programming instructions
QS4 Technical Reference Manual
4.7
Step 7:
Edit the default alarm
messages
Note:
The dialer automatically sends
the default alarm message for active
alarm inputs that are not programmed
to initiate a dialer response.
1. Choose Default Msgs > Alarm.
2. Choose Account then select the subscriber account you
want to receive the message.
3. Choose Active Msg then enter the message you want sent
for alarm activation events.
For example, for Contact ID enter 111000000
4. Choose Restore Msg then enter the message you want
sent for alarm restoration event.
For example, for Contact ID enter 311000000
5. Choose Exit.
Step 8:
Edit the default trouble
messages
Note:
The dialer automatically sends
the default trouble message for inputs
that signal a trouble but are not
programmed to initiate a dialer
response.
1. Choose Default Msgs > Trouble.
2. Choose Account then select the subscriber account you
want to receive the message.
3. Choose Active Msg then enter the message you want sent
for trouble activation events.
For example, for Contact ID enter 130000000
4. Choose Restore Msg then enter the message you want
sent for trouble restoration event.
For example, for Contact ID enter 330000000
5. Choose Exit.
Step 9:
Edit the default supervisory
messages
Note:
The dialer automatically sends
the default supervisory message for
active supervisory inputs that are not
programmed to initiate a dialer
response.
1. Choose Default Msgs > Supervisory.
2. Choose Account then select the subscriber account you
want to receive the message.
3. Choose Active Msg then enter the message you want sent
for supervisory activation events.
For example, for Contact ID enter 120000000
4. Choose Restore Msg then enter the message you want
sent for a supervisory restoration event.
For example, for Contact ID enter 220000000
5. Choose Exit.
Technical Manuals Online! - http://www.tech-man.com