Programming instructions
QS4 Technical Reference Manual
4.5
Step 3:
Assign Panel ID numbers to
the remote annunciator panels
On each remote annunciator panel:
1. Press Menu.
2. Choose Login then enter the password required for Level 4
access (default is 4444).
3. Choose Program > Configure > AutoLearn.
4. Press Del twice then enter an unused Panel ID from 02 to
09 (01 is reserved for the control panel).
5. Enter the number of panels that are connected to the
RS485 riser, including the control panel. This is your
maximum number of panel addresses.
6. Select the wiring configuration of the RS485 riser (Class A
or Class B) then press Enter.
Note:
The wiring configuration must be the same for all
panels.
Step 4:
AutoLearn the control panel.
Note:
Before running the AutoLearn
utility, make sure you have not
installed more cards than the system
allows.
On the control panel:
1. Press Menu.
2. Choose Login then enter the password required for Level 4
access (default is 4444).
3. Choose Reports > Revision > Enter > Display. Verify all the
cards installed in the cabinet appear in the list.
4. Press Menu then choose Program > Configure >
AutoLearn.
5. Enter 01 for the Panel ID.
6. Enter the number of panels that are connected to the
RS485 riser, including the control panel. This is your
maximum number of panel addresses.
7. Select the wiring configuration of the RS485 riser (Class A
or Class B) then press Enter.
If you do not have a DLD card installed, the system will
automatically reboot after the AutoLearn utility configures the
system. Go to step 10.
If you do have a DLD card installed, go to step 5.