Programming instructions
QS4 Technical Reference Manual
4.13
Customizing the system configuration
You can customize the system configuration, if
your requirements exceed that of the general
alarm system created using the AutoLearn and
AutoLoop utilities.
Before you can make any changes to the system
programming, you must log onto the system to
start an editing session.
The control panel has a watchdog timer that kicks
you out of an editing session after a period of
inactivity. If this happens, you will have to log in
again to continue.
After you finish customizing the system
configuration, save your changes, and then test
the system. After everything checks out then Save
and Sync to copy the database to the remote
annunciators.
WARNING:
Entering Edit mode (choosing
Configure on the Program menu) disables the
control panel and leaves the premises unprotected
until you exit Edit mode.
To start an editing session:
1. Press Menu.
2. Choose Login then enter the password required
for Level 4 access.
3. Choose Program > Configure.
What is it you want to do
This is how you do it
Make information about the installer available
on the CPU/Display
AutoLearn default:
No text
1. On the Configure menu, choose System > User
Labels.
2. Choose Facility Name, scan in the name of the
project, and then press Enter.
3. Choose Inst Company, scan in the name of the
installing company, and then press Enter.
4. Choose Phone Number, scan in the telephone
number to call for service-related issues, and
then press Enter.
5. Choose Programmer, scan in the name of the
person that programmed the system, and then
press Enter.
6. Choose Exit.
Set how long notification circuits must stay on
before pressing Alarm Silence can turn them
off or pressing Reset can reset the panel
AutoLearn default:
None (no delay)
1. On the Configure menu, choose System >
ALM/RST Inhib.
2. Select a time delay from the pick list then press
Enter.
Set how long the panel must wait before
signaling an ac power failure
AutoLearn default:
0 (no delay)
1. On the Configure menu, choose System > AC
Power Dly.
2. Select a time delay from the pick list then press
Enter.