Programming instructions
4.16
QS4 Technical Reference Manual
What is it you want to do
This is how you do it
Change the Alarm Verification setting of a
smoke detector
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the detector's serial
number.
3. Choose Verification then choose the length of
the alarm verification period.
4. Choose Exit > Save Edits.
Change the Prealarm setting of a smoke
detector
WARNING:
Prealarm obscuration levels below
80% should not be used without full knowledge of
the possible consequences.
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the serial number of the
detector.
3. Choose Pre-Alarm then choose the warning
threshold setting you want the detector to use.
Refer to Table 4-5 and Table 4-6.
4. Choose Exit > Save Edits.