GA-02.035-EN-30.05.17
Page 6 of 46
gACC-499E/U Communication unit
gACC-499E_U_Manual_EN.doc
DIP switch function: Active at position ON
All switches are in OFF position at delivery,
xcept for DIP switch 7. This will save energy of the batteries.
The internal clock will keep running at normal operating mode.
2.3
Battery connectors
The gACC-499 E/U is equiped with 6 battery connectors.
These are divided into 2 groups.
MAIN POWER
Group1: Connector 1.1; 1,2; 1,3 and 1,4 Main Power
RESERVE POWER
Group 2: Connector 2.1; and 2.2 Back-up and clock power
When applying 2 battery packs, connector 1.1 is used for main
power, and 2.2 is used for back-up.
2.4
Terminals intrinsically safe side
Terminal EX-499-UW Function
1 GND
Signal line -
2 Encoder signal
Signal line +
3 GND
Signal line gAVC 1200 XP2 terminal B
4 UniWire
Signal line gAVC 1200 XP2 terminal A
9 GND
Signal line - (only possible with Safety Barrier channel 4)
10 Pulse signal
Signal line + (only possible with Safety Barrier channel 4)
Connection Encoder or gAVC 1200 or Pulse
Encoder
gAVC 1200
Puls
1 NAMUR (-)
3 UniWire B (klem XP2)
9 GND
2 NAMUR (+)
4 UniWire A (klem XP2)
10 Pulse signal
The PA-terminals are to be connected to the PA-connection of the installation.
This can be done by using 4mm
2
yellow/green wire or by using 2 wires of
1,5mm
2
.
2.5
Power supply
2.5.1
Battery supply
The standard battery supply consists of 2 identical battery packs with each
pack containing 2 Lithium batteries connected in series. The operating
voltage is 7,2 Vdc. The battery pack that is connected to connector 1.1 will
be used first for the modem and the battery pack that is connected to
connector 2.2 will be used for the internal clock. After pack 1.1 is
consumed it will switch to pack 2.2. For certain applications additional
battery packs can be applied. These will be connected to connectors 1.2;
1.3 and/or 1.4.
An additional pack can be connected to connector 2.1 for extended back-
up.
Warning:
Always use batteries of the same type
DIP switch
Battery connectors
PA terminals
Summary of Contents for gACC-499E/U
Page 41: ...GA 02 035 EN 30 05 17 Page 41 of 46 gACC 499E U Communication unit gACC 499E_U_Manual_EN doc ...
Page 42: ...GA 02 035 EN 30 05 17 Page 42 of 46 gACC 499E U Communication unit gACC 499E_U_Manual_EN doc ...
Page 43: ...GA 02 035 EN 30 05 17 Page 43 of 46 gACC 499E U Communication unit gACC 499E_U_Manual_EN doc ...
Page 44: ...GA 02 035 EN 30 05 17 Page 44 of 46 gACC 499E U Communication unit gACC 499E_U_Manual_EN doc ...