T1 CrossConnect Installation & Operation Manual
3 – Installation & Wiring
Version 2
3-16
GatesAir
Intraplex Products
connector). Figures 3-17 through 3-20 (in Section 3.4.5.3) show the typical power connections for the
CrossConnect products.
3.4.5.2 Power Connections
To make connections for power and alarms, perform these steps:
1.
Connect the GND screw to station ground.
2.
If the shelf is AC-powered, verify that the AC cord is available. Do not plug the cord into the AC
source yet.
3.
If the shelf is DC-powered
a.
Verify that a 2A slow-blow external fuse is available in the DC power line to protect the
multiplexer. Remove this fuse and do not replace it until you are ready to power up the shelf.
Warning!
This fuse must be installed, both to protect the multiplexer and to provide a safe means of
removing power from a DC-powered shelf.
b.
Connect the -BAT terminal to the negative terminal of the station battery.
c.
Connect the +BAT terminal to the positive terminal of the station battery, tied to ground.
4.
If the shelf contains one or more Foreign Exchange Station End modules, used for Automatic Ring
Down or Off Premise Extension, connect RING GEN to external ringing generator or loop current
source.
Warning!
When using an external ring generator, place a 0.5A slow-blow fuse in line. For safety
reasons, this fuse must be installed unless the back of the multiplexer will be enclosed.
5.
If the shelf contains one or more of these modules, connect SIG BAT to signaling battery:
•
Foreign Exchange Station End modules
•
4-wire E&M voice modules using signaling
Check with Intraplex Customer Service if you are not sure whether this battery is necessary.
6.
If the shelf is DC-powered, connect SIG BAT to -BAT R. A separate signaling battery is not
required.
Warning!
When using a separate signaling battery, place a slow-blow fuse in line. The value of the
fuse should be 1A for up to 12 voice circuits or 2A for 13 to 24 circuits. For safety reasons,
this fuse must be installed unless the back of the multiplexer is enclosed.
7.
If ALARM and ALERT contacts are to be used, connect the desired contacts to terminal strip 2.