to reset the alarm . Interval of the acoustic alarm:
10s. Different tone sequences when exceeding or
falling below the limit value.
12. Salinity-Alarm (Sound):
a. Off: no acoustic alarm
b. On: acoustic alarm when the TW is switched on
c. Temp: acoustic alarm when the TW is switched
on and the temperature is> 90 ° C
d. Lift: acoustic alarm if TW is switched on, temp.>
90 ° C and a HUB is active.
13. Interval time for contactor control (only witht
relay operation, not with SSR):
The interval time can be set from 2 to 60 seconds.
The following settings then apply:
a. Interval time: 2-9 sec., If the temperature
deviates by> 1 ° C, heating takes place.
b. Interval time: 10-19 sec., If the temperature
deviates by> 2 ° C, heating takes place.
c. Interval time: 20-60 sec., If the temperature
deviates by> 4 ° C, heating takes place.
14. Dry run monitoring:
The drying cycle monitoring can be switched on
or off.
15. Demo-Mode:
If the demo mode is activated (20-240 seconds),
a key press is simulated after the set time. First a
key press „PROG1“ and the next time a key press
„PROG3“ is simulated. The programmed time will
run down normally and then the time (demo
mode time) will be waited until the next key is
simulated. A program can be canceled at any time.
This demo mode is intended for a long-term test
or for a demonstration during presentations.
16. ABCD-Bus (Sicotronic Energy management): The
ABCD interface for energy management can be
switched on or off via the menu (changeable para-
meters) for controls that do not have a ball valve
(SW2-3) or a lifting motor (SW1-8). If the control
has neither a ball valve nor a lift motor, the lift
motor 2 OPEN relay is used as output A.
When the ABCD bus is activated (changeable
parameters) it is not monitored whether a ball
valve or lifting motor has been activated with the
DIP switches or not.
17. Time for the HUB motor movement:
The time can be set between 3:00 and 10:00
seconds. The 50/60 Hz DIP switch no longer has
any function. This option is only possible from
version 8.72
ABCD interface for Sicotronic EAM-N module::
A (Pin 2)
Relay ball valve (230VAC)
Gastro8 is switched on
Relay lift motor 2 open (230VAC)
B (Pin 12) Relay heating (230VAC)
Heating should be on
C(*)
Ext.relay/contactor (230VAC) The relay contact must be the control line from the SSR
or interrupt contactor
D (Pin 13) Neutral conductor (N) PE (Pin 15)
Protective conductor