MDE-4813D CFN PLUS Installation Manual
·
February 2018
26
Table 2-2. CFN PLUS, Cable Types
No.
Function
Type
1
AC Power from Office
Power cable, 3x1.5 mm
2
NYY (14 AWG), in
accordance with local standards
Control to pumps (valves or engine)
In-use signal
2
Coil (Barrier)
Data communication cable, 300 V RMS, 90ºC,
shielded twisted pair, oil resistant, 24 AWG,
low capacitance below 60 PF/meter similar to
Belden 9729 cable
Pulser
TLG (RS-232)
3
LAN
CAT-5E, Shielded, 300 V RMS, 90ºC similar
to Belden 121700 A
4
GND
Ground cable 0.4” (10.8 mm
2
)
2-6.3. Cables Routing
Route the cables from the peripherals and the Office to CFN PLUS as listed in
. Proceed as follows:
Table 2-3. CFN PLUS, Cable Routing
No.
Functional Description
From
Through Insert
Cable Type (*)
1
Power AC
Office
High voltage conduit
1
2
GND
Office
High voltage conduit
4
3
TLG
Office
Low voltage conduit
2
4
LAN
Office
Low voltage conduit
3
5
Control, Pump A
Pump A High voltage conduit
1
6
In-use, Pump A
Pump A High voltage conduit
1
7
Pulser, Pump A
Pump A Low voltage conduit
2
8
Barrier coil, Pump A
Pump A Low voltage conduit
2
(*) Refer to