Part Number 4532415 Rev 5 12/15 17
Typical Applications
In this section you will find examples of the most common
installations for the induction appliance.
A quad model is shown in the illustrations as an example.
When multiple appliances are installed into the same
counter, special attention must be paid to the ventilation
and electrical requirements. Use the list of features below as
your design guideline to ensure a proper cabinet is used for
the application and installation.
IMPORTANT DESIGN FEATURES
Install the Induction Generator in a separate
compartment away from heat and moisture. Ensure to
have adequate ventilation:
1
The air intake vent is located at the front and the
intake air is filtered by an air filter mounted on the
cabinet.
2
The exhaust vent is located at the back of the
generator. Consider to create a baffle to prevent the
exhaust air from mixing with the fresh intake air. As an
alternative, create an exhaust air plenum.
In each of the application example, a baffle is placed
behind the generator and the exhaust is vented into
a separate channel or chamber and then outside the
cabinet. Distance between the exhaust openings and
any obstruction is minimum 40mm [1.57”].
3
Louvered openings of ventilation fan allow exhaust
to escape.
4
Louvered openings or ventilation gap facilitate
proper air-flow.
Safe electrical environment:
5
An enclosed compartment protects the electronic
appliance and wiring from the environment.
Personnel are also protected from the electronics and
the electrical cables.
6
It is important that the coil cables are routed
separately from other communication and power
cables.
7
The appliance is intended to be permanently
connected to fixed wiring. Other means for
disconnection from power supply, such as circuit
breaker or disconnect switch, must be accessible.
NOTE: National and local electrical codes dictate the
electrical requirements. Consult your local authorities
or your electrical contractor for details.
8
Supply inlet / conduit opening shown.
Flexible configuration:
9
The control unit can be installed in multiple
orientations. See Cut-out Dimensions: Holes and Studs
for Control / Operation unit on page 27
10
The generator can be installed up to 3-meter [10-
fee] from the cooktop. See Electrical Cables on page
Water-tight environment:
11
Mating surfaces between the appliance and
coutertop are sealed with silicone (not shown, see
Installation Instructions on page 32).
12
Design and construct ventilation gaps that
could prevent water ingress (not shown, see Cabinet