background image

GSRN10-2250A-SM 

Page 9 of 10 

ENGINEERING DATA 

Model GSRN

 

10 

20 

25 

40 

50 

75 

100 

125 

150 

200 

250 

300 

Capacity in SCFM @  
100 PSIG, 100°F Inlet & 100°F Ambient 

10 

20 

25 

40 

50 

75 

100 

125 

150 

200 

250 

300 

Min. / Max. Inlet Pressure  

30 PSIG (2.1 kgf/cm²)   /  220 PSIG (16.2 kgf/cm²) 

Max. Inlet Temperature  

120°F (48.8°C) 

Min. / Max. Ambient Temperature  

50°F (10°C) / 110°F (43.3°C) 

Inlet / Outlet Connections (NPT) 

3/8 OD 

1/2” 

1/2” 

1/2” 

3/4” 

3/4” 

1” 

1” 

1-1/4” 

1-1/4” 

1-1/2” 

2” 

Delta Pressure / 

P  (PSID) 

@ Std. Rated Conditions 

2.0 

1.5 

1.7 

1.7 

1.9 

2.7 

3.0 

3.5 

2.4 

3.4 

3.4 

3.9 

Product Weight 

 

105 

118 

123 

165 

170 

249 

258 

265 

267 

315 

321 

Refrigeration Compressor Type 

Non Cycling, Hermetic Type 

Refrigeration Compressor Horsepower 

1/7 

1/7 

1/5 

1/4 

1/3 

1/2 

5/8 

3/4 

3/4 

1-1/2 

1-1/2 

Ref. Compressor BTU/H @  
35°F Evaporator & 100°F Ambient 

969 

969 

1880 

2250 

2250 

4142 

5400 

6120 

6120 

9550  12084 

12084 

Watts @ 35°F Evap. & 100°F Amb. 

210 

210 

330 

410 

570 

850 

1080 

1180 

1180 

1450 

2270 

2270 

Refrigerant Suction Pressure

 

28-34 PSIG 

69-81 PSIG 

Refrigerant Type

 

R134a 

R404A 

Refrigerant Charge 

4 oz. 

4 oz. 

8 oz. 

10 oz. 

13 oz. 

13 oz. 

3 Lbs. 

4 Lbs. 

4 Lbs. 

5 Lbs. 

7 Lbs. 

7 Lbs. 

Nominal Voltage (Min-Max Range) 

115-1-60

 (103-126) 

Min. Circuit Ampacity 

 

2.8 

5.0 

6.6 

7.7 

12.4 

15 

17 

17 

Not Available 

Maximum Fuse Size (Amps) 

 

15 

15 

15 

15 

15 

20 

20 

20 

Not Available 

RLA: Rated Load Amps 

 

1.9 

3.7 

4.9 

5.8 

9.5 

11.3 

14.4 

14.4 

Not Available 

LRA: Locked Rotor Amps 

 

14.4 

29 

27.5 

32 

48.0 

58.8 

69.0 

69.0 

Not Available 

Nominal Voltage (Min-Max Range) 

230/208-1-60

 (187-253) 

Min. Circuit Ampacity 

Not Available 

6.3 

7.8 

10.4 

11.7 

11.7 

Maximum Fuse Size (Amps) 

Not Available 

15 

15 

15 

15 

20 

20 

20 

RLA: Rated Load Amps 

Not Available 

4.8 

5.9 

7.7 

7.7 

8.1 

9.5 

9.5 

LRA: Locked Rotor Amps 

Not Available 

23 

27.4 

41.8 

41.8 

41 

51 

51 

Overload 

External “Klixon” Thermal and Current (Auto Reset) 

 

Model GSRN

 

250  300  400  500 

650 

800  1000  1200  1500  1750  2000  2250 

Capacity in SCFM @  

100 PSIG, 100°F Inlet & 100°F Ambient 

250 

300 

400 

500 

650 

800 

1000 

1200 

1500 

1750 

2000 

2250 

Min. / Max. Inlet Pressure 

30 PSIG (2.1 kgf/cm²) / 220 PSIG 

30 PSIG (2.1 kgf/cm²)   /  150 PSIG (10.6 kgf/cm²) 

Max. Inlet Temperature 

120°F (48.8°C) 

Min. / Max. Ambient Temperature 

50°F (10°C) / 110°F (43.3°C) 

Inlet / Outlet Connections (NPT) 

1-1/2” 

2” 

2” 

2” 

2” 

3” 

3” 

3” 

4” Flg 

4” Flg 

4” Flg 

4” Flg 

Delta Pressure / 

P  (PSID) 

@ Std. Rated Conditions 

3.4 

3.0 

3.7 

3.8 

3.9 

3.7 

3.9 

4.2 

3.9 

4.0 

4.2 

4.4 

Shipping Weight 

315 

321 

350 

549 

555 

920 

1009 

1200 

1600 

1611 

1980 

2115 

Refrigeration Compressor Type 

Non Cycling, Hermetic Type 

Refrigeration Compressor Horsepower 

1-1/2 

1-1/2 

10 

10 

Ref. Compressor BTU/H @  

35°F Evaporator & 100°F Ambient 

12084 

12084 

14544 

26832 

26832 

36624 

47904 

60540 

74868 

74868 

87984 

8798

Watts @ 35°F Evap. & 100°F Amb. 

2270 

2270 

2743 

5169 

5169 

5710 

7544 

10070 

11760  11760  15210 

1521

Refrigerant Suction Pressure 

69-81 PSIG 

Refrigerant Type 

R404a 

Refrigerant Charge  

7 Lbs. 

7 Lbs. 

7 Lbs. 

7 Lbs. 

7 Lbs. 

18 Lbs.  22 Lbs.  24 Lbs.  40 Lbs.  40 Lbs.  40 Lbs.  40 Lbs. 

Condenser Fan Switch  
Pressure Settings 

Primary = Cut In: 300 / Cut Out: 250 

Primary = Cut In: 265 / Cut Out: 215     

Secondary = Cut In: 300  /  Cut Out: 250  

Overload 

Internal Thermal and Current (Auto Reset) 

Nominal Voltage  (Min- Max Range) 

230/200-3-60   

(180-253)

 

Min. Circuit Ampacity 

9.2 

9.2 

10 

19.4 

19.4 

19.6 

26.6 

35.4 

38.2 

38.2 

47.1 

47.1 

Maximum Fuse Size (Amps) 

15 

15 

20 

30 

30 

35 

45 

70 

70 

70 

90 

90 

RLA: Rated Load Amps 

7.6 

7.6 

8.2 

15.9 

15.9 

17.1 

23.4 

30.5 

35.1 

35.1 

42.2 

42.2 

LRA: Locked Rotor Amps 

38 

38 

38 

98 

98 

117 

128 

155 

157 

157 

210 

210 

Nominal Voltage  (Min- Max Range) 

460-3-60   

(414-506)

 

Min. Circuit Ampacity 

4.6 

4.6 

5.4 

9.1 

9.1 

10.2 

13.1 

15.5 

19.5 

19.5 

23.1 

23.1 

Maximum Fuse Size (Amps) 

10 

10 

10 

15 

15 

20 

25 

30 

35 

35 

40 

40 

RLA: Rated Load Amps 

3.8 

3.8 

4.4 

7.5 

7.5 

8.9 

11.8 

13.7 

17.9 

17.9 

21.1 

21.1 

LRA: Locked Rotor Amps 

16 

16 

16 

38 

38 

42 

67 

80 

90 

90 

105 

105 

Nominal Voltage  (Min- Max Range) 

575-3-60   

(546-603) 

Min. Circuit Ampacity 

4.1 

4.1 

4.8 

9.1 

9.1 

9.5 

11.66 

13.8 

17.37 

17.37 

20.9 

20.9 

Maximum Fuse Size (Amps) 

15 

15 

15 

15 

15 

20 

30 

30 

50 

50 

50 

50 

Total Amperage 

3.04 

3.04 

3.52 

7.12 

9.44 

10.96 

14.32 

14.32 

16.88 

16.88 

LRA: Locked Rotor Amps 

16 

16 

16 

38 

38 

42 

67 

80 

90 

90 

105 

105 

 

Summary of Contents for GSRN Series

Page 1: ...NG STANDARD Contents Introduction Page 2 General Safety Warnings Page 2 Proper Use of the Dryer Page 3 Receiving Equipment Page 3 Installation Location and Piping Page 3 Recommended System Design Page...

Page 2: ...00 682 9868 Failure to install the compressed air dryer per this manual or any change to the dryer not previously authorized by the manufacture will void the warranty The information and specification...

Page 3: ...be located on a level floor or shelf free from vibrations and sufficient to support the total weight of the machinery Although the dryer package is a freestanding unit it may be secured by bolting th...

Page 4: ...100 F 37 7 C 105 F 40 5 C 110 F 43 3 C 115 F 46 1 C 120 F 48 8 C Additional Load 0 15 32 51 75 The pipe connection to the dryer should match the standard connection ports provided The chart below is p...

Page 5: ...ssembly GSRN 50 through GSRN 2250 When maintaining float drains depressurize the dryer drain prior to work initiation Drain line and Drain Connector must be removed prior to bowl and float drain remov...

Page 6: ...0 PSIG for two fan units If the suction analyzer or discharge gauge is not in the specified range contact your local distributor GSRN 100W through GSRN 200W The water cooled series GSRN 100W through G...

Page 7: ...y discharging condensate and air from the drain tube try replacing the solenoid valve diaphragm or the complete drain valve As Required MODEL CAPACITY CORRECTION MULTIPLIER Inlet Temp 90 F 100 F 110 F...

Page 8: ...rize dryer and replace or clean drain strainer 2 Solenoid valve or electronic timer failure Replace drain solenoid and or timer assembly C Drain System Failure with continuous condensate or air discha...

Page 9: ...1200 1500 1750 2000 2250 Min Max Inlet Pressure 30 PSIG 2 1 kgf cm 220 PSIG 30 PSIG 2 1 kgf cm 150 PSIG 10 6 kgf cm Max Inlet Temperature 120 F 48 8 C Min Max Ambient Temperature 50 F 10 C 110 F 43 3...

Page 10: ...to investigate and inspect any assumed defects At seller s option buyer must return any defective materials to seller s plant or authorized depot at buyer s expense Freight charges for returned or rep...

Reviews: