STARTUP PROCEDURE 

 

GSRN-20A through GSRN-200A 

Energize the refrigeration compressor by placing the “on/off” dryer switch with indicating light to the “on (I)” 
position. The refrigerant compressor and fan motor will begin to operate. The suction/analyzer gauge will 
fall to a range of 28-35 PSIG. If the suction/analyzer gauge is not in the specified range, contact your local 
distributor. 
 

 

GSRN-250-2250 or any 3-Phase powered unit 

REQUIRE AN 8 HOUR CRANK CASE WARMUP PRIOR TO STARTUP

 

To prevent equipment damage the unit must have primary power applied with the “on/off” 
switch in the “OFF (0)” position for no less than 8 hours. This energizes the crank case heater 
to allow any liquid refrigerant in the crankcase to be vaporized prior to startup.  Energizing 
the dryer prior to crank case heating can “wash away” compressor lubricants and will cause 
premature compressor failure.  

 

GSRN-250A through GSRN-2250A 

Energize the refrigeration compressor by placing the “on/off” dryer switch with indicating light to the “on (I)” 
position. The refrigerant compressor and fan motor will begin to operate. The suction/analyzer gauge will 
fall to an upper (RF) orange pie range of 73-82 PSIG and the discharge gauge will raise to a range of 190 
to 382 PSIG. These units are equipped with condenser fan cycle controls and operate independent of the 
compressor. Each fan is controlled via a refrigeration discharge pressure switch (260-200 PSIG) for single 
fan  units  and  (290-240  PSIG)  for  two  fan  units.  If  the  suction/analyzer  or  discharge  gauge  is  not  in  the 
specified range, contact your local distributor. 
 

GSRN-100W through GSRN-200W 

The water-cooled series GSRN-100W through GSRN-200W utilizes a city or tower fluid supply. The unit is 
supplied with a water-regulating valve at the outlet of the refrigeration condenser. This valve modulates 
water  flow  to  maintain  a  stable  refrigerant  discharge  pressure  of  125-145  PSIG.  If  the  refrigeration 
discharge pressure maintains a pressure above or below this setting, adjustments will be required to the 
water-regulating valve. Contact your local distributor. 
 

GSRN-250W through GSRN-2250W 

The water-cooled series GSRN-250W through GSRN-2250W utilizes a city or tower fluid supply. The unit 
is supplied with a water-regulating valve at the outlet of the refrigeration condenser. This valve modulates 
water  flow  to  maintain  a  stable  refrigerant  discharge  pressure  of  250-275  PSIG.  If  the  refrigeration 
discharge pressure maintains a pressure above or below this setting, adjustments will be required to the 
water-regulating valve. Contact your local distributor. 
 
 

SHUT DOWN PROCEDURE 

When the dryer is to be shut down for service, maintenance, or other reasons switch the dryer off by placing 
the “on/off” dryer switch with indicating light to the “OFF (0)” position.  If service or maintenance is required 
disconnect  and  lockout  the  main  power  supply,  isolate  and  depressurize  the  internal  compressed  air 
pressure to atmosphere prior to commencement of any work. 

 

If  the  shutdown  resulted  in  loss  of  main  power  interruption,  repeat  start  up  procedure  so  crank 
case heater has time to raise the crank case temperature. 
 

 

 

Summary of Contents for GSRN Series

Page 1: ...NG STANDARD Contents Introduction Page 2 General Safety Warnings Page 2 Proper Use of the Dryer Page 3 Receiving Equipment Page 3 Installation Location and Piping Page 3 Recommended System Design Page...

Page 2: ...00 682 9868 Failure to install the compressed air dryer per this manual or any change to the dryer not previously authorized by the manufacture will void the warranty The information and specification...

Page 3: ...be located on a level floor or shelf free from vibrations and sufficient to support the total weight of the machinery Although the dryer package is a freestanding unit it may be secured by bolting th...

Page 4: ...100 F 37 7 C 105 F 40 5 C 110 F 43 3 C 115 F 46 1 C 120 F 48 8 C Additional Load 0 15 32 51 75 The pipe connection to the dryer should match the standard connection ports provided The chart below is p...

Page 5: ...ssembly GSRN 50 through GSRN 2250 When maintaining float drains depressurize the dryer drain prior to work initiation Drain line and Drain Connector must be removed prior to bowl and float drain remov...

Page 6: ...0 PSIG for two fan units If the suction analyzer or discharge gauge is not in the specified range contact your local distributor GSRN 100W through GSRN 200W The water cooled series GSRN 100W through G...

Page 7: ...y discharging condensate and air from the drain tube try replacing the solenoid valve diaphragm or the complete drain valve As Required MODEL CAPACITY CORRECTION MULTIPLIER Inlet Temp 90 F 100 F 110 F...

Page 8: ...rize dryer and replace or clean drain strainer 2 Solenoid valve or electronic timer failure Replace drain solenoid and or timer assembly C Drain System Failure with continuous condensate or air discha...

Page 9: ...1200 1500 1750 2000 2250 Min Max Inlet Pressure 30 PSIG 2 1 kgf cm 220 PSIG 30 PSIG 2 1 kgf cm 150 PSIG 10 6 kgf cm Max Inlet Temperature 120 F 48 8 C Min Max Ambient Temperature 50 F 10 C 110 F 43 3...

Page 10: ...to investigate and inspect any assumed defects At seller s option buyer must return any defective materials to seller s plant or authorized depot at buyer s expense Freight charges for returned or rep...