This  dryer  has  been  designed,  manufactured  and  tested  to  separate  humidity  normally  contained  in 
compressed air 

only

. Any other unauthorized use will be considered improper. The manufacturer will void 

the  warranty  and  not  be  held  responsible  for  any  problem  arising  from  improper  use.  The  correct  use 
requires adherence to installation conditions specified in this manual. 
 
This dryer is supplied tested and fully assembled. The only operation left to the user is the connection to 
the plant in compliance with the instructions given in the following chapters.  

 

RECEIVING EQUIPMENT 

Immediately  upon  receipt  of  equipment,  remove  all  crating  and  packaging  around  equipment.  Examine 
machinery for any damages either external or internal that may have occurred in transit. 
 
If there is any physical damage or a refrigerant leak, 

(suction/analyzer gauge reads zero)

 please note 

all damages on bill of lading during delivery. If damage is detected after the equipment delivery; contact 
the local terminal to report all damages and file a claim immediately with the transportation company. The 
carrier is legally responsible for any damages, since the unit is shipped F.O.B.  
 

INSTALLATION LOCATION  PIPING & CONNECTION 

 

Particular  care  is  required  in  selecting  the  installation  site,  as  an  unsuitable  location  could 
jeopardize the proper operation of the dryer. This unit is not suitable to be used in an explosive 
atmosphere, or where the risk of fire could be present. 

 
The  unit  should  be  installed  in  an  area  that  is  clean  and  dry,  allowing  sufficient  space  on  all  sides  for 
routine  maintenance  and  service. It  should  be  located  on  a  level  floor  or  shelf  free  from  vibrations  and 
sufficient to support the total weight of the machinery.  Although the dryer package is a freestanding unit, 
it may be secured by bolting the base to the floor but is not required. 

This standard dryer is designed 

for

 

indoor installation

.  Contact distributor if installing unit outdoors. 

 
Installations at altitudes above 4000 feet (1219 meters) will experience a loss of capacity and may require 
field adjustments of pressure settings.  The unit has been factory adjusted to operate up to 4000 feet (1219 
meters), and if installation is above this altitude, contact your local distributor for correct refrigerant settings. 

 
Air-Cooled Units 

Allow  (2’)  two  feet,  minimum  clearance  around  the  dryer  for  maintenance  access  and  adequate  free 
circulation of cooling air to the dryer. The ambient temperature around the dryer must not exceed 110°F 
(37.7°C) or be less than 40°F (10°C).  
 

Water-Cooled Unit & Y-Strainer Installation 

The fluid supply lines to the condenser should be sized to deliver the required flow of coolant. If the ambient 
temperature exceeds the supply fluid temperature by 10°F, insulate the inlet line to the condenser. Cooling 
fluid quality should be well maintained with proper water treatment and a low differential across the inlet 
filtration.    If  cooling  supply  lines  are  exposed  to  ambient  that  exceed  the  fluid  temperature  by  10°F  the 
addition of insulation will help maintain the fluid cooling capacity. 
 

Condenser Cooling Water Supply Requirements 

Fluid Temperature 

60°F(15.6°C) to 90°F(32.2°C)  

Filtration 

16-20 mesh strainer 

pH 

6.6 to 7.2 

 
Ambient temperatures below 40°F (10°C) require optional equipment specified below. Sufficient ventilation 
must  be  provided  to  maintain  acceptable  ambient  for  efficient  operation.  Consider  heat  rejection  when 
locating dryer.  
 

 

Summary of Contents for GSRN Series

Page 1: ...NG STANDARD Contents Introduction Page 2 General Safety Warnings Page 2 Proper Use of the Dryer Page 3 Receiving Equipment Page 3 Installation Location and Piping Page 3 Recommended System Design Page...

Page 2: ...00 682 9868 Failure to install the compressed air dryer per this manual or any change to the dryer not previously authorized by the manufacture will void the warranty The information and specification...

Page 3: ...be located on a level floor or shelf free from vibrations and sufficient to support the total weight of the machinery Although the dryer package is a freestanding unit it may be secured by bolting th...

Page 4: ...100 F 37 7 C 105 F 40 5 C 110 F 43 3 C 115 F 46 1 C 120 F 48 8 C Additional Load 0 15 32 51 75 The pipe connection to the dryer should match the standard connection ports provided The chart below is p...

Page 5: ...ssembly GSRN 50 through GSRN 2250 When maintaining float drains depressurize the dryer drain prior to work initiation Drain line and Drain Connector must be removed prior to bowl and float drain remov...

Page 6: ...0 PSIG for two fan units If the suction analyzer or discharge gauge is not in the specified range contact your local distributor GSRN 100W through GSRN 200W The water cooled series GSRN 100W through G...

Page 7: ...y discharging condensate and air from the drain tube try replacing the solenoid valve diaphragm or the complete drain valve As Required MODEL CAPACITY CORRECTION MULTIPLIER Inlet Temp 90 F 100 F 110 F...

Page 8: ...rize dryer and replace or clean drain strainer 2 Solenoid valve or electronic timer failure Replace drain solenoid and or timer assembly C Drain System Failure with continuous condensate or air discha...

Page 9: ...1200 1500 1750 2000 2250 Min Max Inlet Pressure 30 PSIG 2 1 kgf cm 220 PSIG 30 PSIG 2 1 kgf cm 150 PSIG 10 6 kgf cm Max Inlet Temperature 120 F 48 8 C Min Max Ambient Temperature 50 F 10 C 110 F 43 3...

Page 10: ...to investigate and inspect any assumed defects At seller s option buyer must return any defective materials to seller s plant or authorized depot at buyer s expense Freight charges for returned or rep...