Centric 3x480 Vac, Installation Guide, rel. 2.2
56
Figure 56: ”Model Type” screen for a 180 kW system
3.
Next you must tell the system the new total number of modules, and how many of them (if any) are
intended to provide redundancy. On the LDC control panel, navigate to
“Setup > System > Number of modules”. Decrease the total number of modules as required, and
indicate how many of the modules are intended to provide redundancy. The
Centric User Guide
provides more information on redundancy.
A password is required to perform this function. If you do not have the required password, contact
your distributor or sales agent.
Figure 57: “Number of modules” screen
4.
From the system main menu, choose "Operation > Turn on/off > Modules off".
5.
On the screen, choose the module to be removed. The modules are numbered from bottom to top.
The outline of the module you choose becomes highlighted.