![Gamatronic Centric 3x480 Vac Installation Manual Download Page 17](http://html1.mh-extra.com/html/gamatronic/centric-3x480-vac/centric-3x480-vac_installation-manual_3327033017.webp)
G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
Centric 3x480 Vac, Installation Guide, rel. 2.2
11
Verify that there is a switch or other means to easily
and safely disconnect the battery cabinet from the
UPS in the event of an emergency or for
maintenance.
The batteries can be easily and
quickly disconnected from the UPS
when necessary.
•
With the battery circuit breaker "OFF" or
the battery fuses removed, connect the
battery cable to the UPS. Leave the
battery circuit breaker "OFF" or leave the
battery fuses out, until instructed to turn
the battery on in section
4.4.1.
•
Verify proper polarity of the battery
connection to the UPS, and verify proper
connection between the two battery
Neutral lines and UPS’s Neutral bus bar.
Batteries are connected and OFF.
4.3.4.4
Power-up the system.
LCD screen is on.
4.3.5
Perform the initial configuration.
Initial configuration completed.
4.4
Complete first-time startup.
First-time startup completed.
4.4.1
If you are using
lithium-ion
batteries, verify that
the battery setup parameters (Setup > Battery) are
appropriate for the batteries you have chosen.
Compare the values of the battery
setup parameters against the
battery manufacturer’s data sheet.
User’s Guide,
“Setup > Battery”
Before turning on the battery, verify that the LED
on the left front of each UPS modules is lit green.
Perform post-startup tests.
Tests successfully completed.
4.5
Comments on site preparation
–
electrical: ___________________________________________________
________________________________________________________________________________________
_________________________________________________________________________________________