Centric 3x480 Vac, Installation Guide, rel. 2.2
35
4.4.1
Continuing first-time start-up process
1.
If you are using lithium-ion batteries, check the values in the “Setup > Battery” parameters against the
information in the battery manufacturer’s data sheet. Verify that the parameter values are appropriate
for the batteries you have chosen.
2.
Verify again that the battery is connected to the UPS and that the battery circuit breaker is in the “ON”
position.
3.
On the
Centric
main menu, choose "Operation > Turn on/off > System on".
4.
Wait until the LED on the left front of each UPS modules is lit green.
This takes may take several minutes.
5.
The two green LEDs on each dc-to-dc module should now be lit green.
6.
Return to the main menu by tapping on the "house" icon in the upper left corner of the
Centric
screen.
7.
On the main menu screen, if the alarm symbol (a red circle) is displayed, press the alarm symbol to
display the potential problems. Refer to the troubleshooting section of this document to determine the
proper response to the alarm indications.
Figure 30: The "alarms" icon indicates alarm conditions
8.
Perform a brief battery test to verify that the
Centric
is ready and able to operate in battery mode
when needed. To perform a battery test, from the main menu choose:
"Operation > Battery test > Test battery". After 1 minute, cancel the test by pressing
"Abort the test > OK".
9.
Verify that the ac output circuit breakers on the electrical board are OFF.
You can now connect a load device to the ac output, then turn ON the ac output circuit breakers on
the electrical board.
10. Now you must update the last maintenance date. From the main menu, choose
"Setup > Time > Set last maintenance date". Tap on the line that says "Last maintenance date". Press
"confirm", and enter the system password if prompted for it.
11. Finally, to save the settings you have defined, from the main menu choose:
"Setup > Save and restore > Save settings > OK".