DUCTIMAX
TECHNICAL MANUAL
14
8 VENTILATION FEATURES
The pressure drops shown below refer to accessories that are
not at all affected by the various sizes of the thermal ventilating
units.
Pressure drops refer to the accessory itself and are not related to
the size of the thermal ventilating units.
CM - CA - CAF
QA m3/h
50
100
150
200
250
300
400
500
600
700
800
900
1000 1100 1200 1300 1400 1500 1600 1700
CM1
DPA
(Pa)
0
1
3
5
8
12
20
31
44
59
-
-
-
-
-
-
-
-
-
-
CM2
0
0
1
1
2
3
5
8
11
14
18
23
28
34
40
46
53
-
-
-
CM3
0
0
0
1
1
1
2
3
5
6
8
10
12
15
18
20
24
27
30
34
CA2
0
0
1
2
3
4
6
10
14
19
24
30
37
44
52
-
-
-
-
-
CA3
0
0
0
1
1
1
3
4
6
7
10
12
15
18
21
24
28
32
36
40
CAF2*
0
1
2
4
6
8
12
18
25
33
41
50
61
-
-
-
-
-
-
-
CAF3*
0
0
1
1
2
3
5
7
10
12
16
19
23
27
32
37
42
47
53
59