Galletti Ductimax Technical Manual Download Page 44

DUCTIMAX

TECHNICAL MANUAL

44

EVO - wall-mounted microprocessor split controller with display

EVO controller is a system composed of:

•  Circuit board comprising the power circuit, the microprocessor system and the removable screw connectors for the connection of the inlet and outlet devices;

•  User interface comprising a graphic display and a keyboard (six keys) provided with clock and sensor to read the ambient temperature.

Main functions:

•  Room air temperature reading and adjustment

•  Room humidity reading and adjustment

•  Water temperature reading (water sensor as an optional)

•  Manual/automatic regulation of the fan speed with ON -OFF step and modulating control

•  Automatic adjustment of valve opening with ON/OFF and modulating controller

•  Manual and automatic switching of heating and cooling mode depending on the water temperature within the heat exchanger or on the room temperature, 

with a selectable neutral zone

•  Clock and hourly timer-programmed operation

•  3 Analogue outputs for controlling modulating evices -10V

•  E conomy function and minimum temperature

•  1 Digital outputs for controlling (On/Off) external devices (novoltage contacts)

•  Serial port for RS485 connection

•  Serial port for OC connection

•  3 digital inputs for ON-OFF, Economy, Operating mode remote setting

Operating mode

The controller is provided with a programmable display that allows you to view and set the hydronic unit functions by means of the specific interface with parameter 

description.

LED503 - Recess wall-mounted microprocessor control

The proposed microprocessor control panels for Galletti indoor units is completed by the LED503 command with LED display that is designed for recess wall 

mounting.

CONTROLLER

The control software developed by the Galletti Software Dept., features:

•  Manual fan speed selection

•  Automatic selection of fan speed according to the difference between the set temperature and the room air temperature

•  Manual selection of heating/cooling operating mode;

•  automatic selection of heating/cooling operating mode;

•  Control of 1 or 2 ON/OFF valves;

•  Control of additional heating element;

•  on board timer function to detect the actual ambient air temperature;

•  Reading of air ambient temperature, set point, fan speed and mode selection on the LED display.

CO (W-G-B) - plate for LED503, white W (RAL 9003), grey G (RAL 7031), black B (RAL 9005)

Covering plates available in three colours matching the 503 connectors.

MCSWE - water temperature sensor for microprocessor controls model EVO, MYCOMFORT

Directly connected to the microprocessor controllers EVO and MYCOMFORT to measure the water temperature through the heat exchanger.

If the temperature registered is lower than 17 °C the unit works in cooling mode and the temperature range of the control panel will be referred to the cooling mode 

(19/31 °C); if the temperature registered is higher than 37 °C the unit works in heating mode and the temperature range of the control panel will be referred to the 

heating mode (14/26 °C). If the temperature registered is between 17 °C e 37 °C the control panel will disable the unit operation.

MCSUE - Humidity sensor for EVO and MYCOMFORT microprocessor controller

Directly connected to the microprocessor controllers EVO and MYCOMFORT, it enables the control of the heating element ventilation (if present, as support in heating 

mode) and the automatic cooling/heating changeover according to the water temperature.

PMA / PMAC - plenum for the connection to flexible dutcs

PMAD e PMACD (insulated) plenums are used to connect to air distribution plants achieved by means of hoses or to other dedicated accessories. They can be 

installed on both the intake and delivery line (in this case the hose should be insulated). The spigot diameter is Ø 200 mm.

DUCTIMAX 1-2: number of outlets 2

DUCTIMAX 3-4: number of outlets 3

DUCTIMAX 5-6: number of outlets 3

PAF - Front air intake plenum Ø200

Thanks to the accessories " PMA outlet plenum" and " PAF front intake plenum " it is possible to include DM in installations where it is necessary to have the air outlet 

and inlet on a single side, thus considerably reducing the required space. The air intake is equipped with Ø 200 collars

RD / RDC - Suction/delivery straight connection

Are used to connect the unit DUCTIMAX to rectangular air distribution ducts or directly to GM and GA air outlet and intake grilles

Summary of Contents for Ductimax

Page 1: ...pipes systems 4 pipes systems Centrifugal fan Ducted PLUS Multi speed motor Heat exchanger up to 4 rows Water connections ABS centrifugal fans Can be integrated into GARDA Incorporable ioniser Medium...

Page 2: ...The CE marking of the product ensures its compliance with the safety requirements of the following directives the Machinery Directive the Electromagnetic Compatibility Directive the Electrical Safety...

Page 3: ...TOR p 5 AIR FILTER p 5 2 1 AIR INTAKE p 5 HEAT EXCHANGER p 5 FANS p 5 3 INSTALLATION p 6 3 1 INSTALLATION REQUIREMENTS p 6 3 2 ASSEMBLY OF UNITS p 7 4 AVAILABLE ACCESSORIES p 8 5 RATED TECHNICAL DATA...

Page 4: ...condensing...

Page 5: ...DUCTIMAX to GARDA Electric heating elements complete with safety devices are available to integrate the hydronic operation The action of the G3 air filter can be combined with an air ioni sation syst...

Page 6: ...d the upper closing panel 3 1 INSTALLATION REQUIREMENTS Some rules to follow Vent air from the exchanger while the pumps are off For this purpose use the air vent valves situated next to the exchang e...

Page 7: ...th a diam eter of 24 mm for each bar so that the rubber anti vibra tion mounts cannot deform or come out of the slot Before tightening the lock nut adjust the main nut so as to assure that the unit is...

Page 8: ...M Aluminium air outlet grille with 2 row fins and subframe Valves V2VDF STD 2 way valves ON OFF or MUDULATING actuator 230V or 24V power supply hydraulic kit for main and additional heat exchanger V2V...

Page 9: ...20 1 60 1 20 1 60 Power supply cable type N07V K Cross section area of power cables 5 mm 1 00 1 00 1 00 1 00 Safety fuse F A 1 1 1 1 Fuses type gG DUCTIMAX 33 34 43 44 Speed min med max min med max m...

Page 10: ...47 relative humidity 3 Water temperature 45 C 40 C air temperature 20 C 4 Sound power measured according to standards ISO 3741 and ISO 3742 5 The shown section is to be considered as the minimum reco...

Page 11: ...m h 333 683 755 333 683 755 1050 1163 1289 1050 1163 1289 Available static pressure DF 1R E Pa 12 50 61 12 50 61 40 50 60 40 50 60 Power input DF 1R E W 76 167 192 76 167 192 235 280 332 235 280 332 M...

Page 12: ...2 6 WEIGHTS DUCTIMAX 13 14 23 24 33 34 43 44 53 54 63 64 Weight standard version kg 24 4 24 4 25 4 25 4 33 0 33 0 36 0 36 0 45 0 45 0 51 0 51 0 Weight DF 1R version kg 25 8 25 8 26 8 26 8 34 6 34 6 37...

Page 13: ...detailed report which includes performances dimensional drawings tender specifications and the economic offer Product selection Filters to make the identification of the requested product easier Perf...

Page 14: ...of the thermal ventilating units CM CA CAF QA m3 h 50 100 150 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 CM1 DPA Pa 0 1 3 5 8 12 20 31 44 59 CM2 0 0 1 1 2 3 5 8 11 14...

Page 15: ...5 51 56 2 53 9 50 2 45 8 42 2 36 2 27 5 6 50 54 2 51 9 48 2 43 8 40 2 34 2 25 5 49 53 2 50 9 47 2 42 8 39 2 33 2 54 2 5 46 52 2 49 9 46 2 41 8 38 2 32 2 21 5 45 49 7 49 5 44 6 42 1 35 8 27 5 17 9 4 4...

Page 16: ...8 42 2 36 2 27 5 5 52 56 2 53 9 50 2 45 8 42 2 36 2 27 5 49 53 2 50 9 47 2 42 8 39 2 33 2 24 5 4 50 54 2 51 9 48 2 43 8 40 2 34 2 25 5 47 51 2 48 9 45 2 40 8 37 2 31 2 22 5 3 45 49 2 46 9 43 2 38 8 35...

Page 17: ...8 42 2 36 2 27 5 51 55 2 52 9 49 2 44 8 41 2 35 2 26 2 6 50 54 2 51 9 48 2 43 8 40 2 34 2 25 5 49 53 2 50 9 47 2 42 8 39 2 33 2 54 2 5 46 50 2 47 9 44 2 39 8 36 2 30 2 21 5 45 49 2 46 9 43 2 38 8 35 2...

Page 18: ...8 42 2 36 2 27 5 5 52 56 2 53 9 50 2 45 8 42 2 36 2 27 5 49 53 2 50 9 47 2 42 8 39 2 33 2 24 5 4 50 54 2 51 9 48 2 43 8 40 2 34 2 25 5 47 51 2 48 9 45 2 40 8 37 2 31 2 22 5 3 45 49 2 46 9 43 2 38 8 35...

Page 19: ...nections additional heat exchanger 1 2 female gas 3 Condensate discharge diameter 17 27 27 35 5 20 196 5 95 263 45 107 300 326 499 545 411 41 92 205 186 79 520 3 2 2 1 15 15 C D A E 603 575 252 300 30...

Page 20: ...r water connections 3 4 gas female 2 Water connections additional heat exchanger 1 2 female gas 3 Condensate discharge diameter 17 1177 713 386 5 597 106 209 221 503 618 109 360 630 282 27 27 1123 685...

Page 21: ...kes are shown on the rating labels on the units During installation strictly abide by the indications on the wir ing diagram for the unit control panel combination See electrical wirings from page 13...

Page 22: ...OMUNE del motore quello di colore BIANCO il suo errato collegamento provoca danni irrepara bili al motore DM1 Wiring diagram L Phase PE Ground N Neutre F Fuse not provided IL Circuit breaker not suppl...

Page 23: ...eaker not supplied Wirings made by supplier WH White BK Nero BU Blue BN Brown GY Grey GN Green YE Yellow RD Rosso GYNE Yellow green ground PE DM6 Wiring diagram L Phase PE Ground N Neutre F Fuse not p...

Page 24: ...Ductimax Technical manual 24 MCB V DM 1 WH M White Neutral BK M Black BU M Blue GY M Grey BN M Brown VT M Purple RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutral...

Page 25: ...artial of this manual is strictly forbidden 25 MCB V dm 2 5 WH M White Neutral BK M Black BU M Blue GY M Grey BN M Brown VT M Purple RD Red YE M Yellow GN M Green BN VC H Brown valve actuator line BU...

Page 26: ...Ductimax Technical manual 26 MCB V DM 6 WH M Bianco BK M Black BU M Blue GY M Grey RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutral...

Page 27: ...02214 05 All copying even partial of this manual is strictly forbidden 27 MCB V RE DM 1 WH M White Neutral BK M Black BU M Blue GY M Grey BN M Brown VT M Purple RD Red WH VC H White valve actuator neu...

Page 28: ...Ductimax Technical manual 28 MCB V RE DM 2 5 WH M Bianco neutro BK M Black GY M Grey YE M Yellow BU M Blue GN M Green BN M Brown RD Red WH VC H White valve actuator neutral...

Page 29: ...UT66002214 05 All copying even partial of this manual is strictly forbidden 29 MCB V RE DM 6 WH M White Neutral BK M Black BU M Blue GY M Grey RD Red WH VC H White valve actuator neutral...

Page 30: ...Ductimax Technical manual 30 MCM MCL V DM 1 WH M White Neutral BK M Black BU M Blue GY M Grey BN M Brown VT M Purple RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutral...

Page 31: ...en partial of this manual is strictly forbidden 31 MCM MCL V DM 2 5 WH M White Neutral BK M Black GY M Grey YE M Yellow BU M Blue GN M Green BN M Brown RD Red BN VC H Brown valve actuator line BU VC H...

Page 32: ...Ductimax Technical manual 32 MCM MCL V DM 6 WH M White Neutral BK M Black BU M Blue GY M Grey RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutral...

Page 33: ...ng even partial of this manual is strictly forbidden 33 MCM MCL V RE DM 1 WH M White Neutral BK M Black BU M Blue GY M Grey BN M Brown VT M Purple RD Red BN VC H Brown valve actuator line BU VC H Blue...

Page 34: ...max Technical manual 34 MCM MCL V RE DM 2 5 WH M White Neutral BK M Black GY M Grey YE M Yellow BU M Blue GN M Green BN M Brown RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neu...

Page 35: ...5 All copying even partial of this manual is strictly forbidden 35 MCM MCL V RE DM 6 WH M White Neutral BK M Black BU M Blue GY M Grey RD Red BN VC H Brown valve actuator line BU VC H Blue valve actua...

Page 36: ...Ductimax Technical manual 36 DM 1 TED2T WH M White Neutral BK M Black BU M Blue GY M Grey BN M Brown VT M Purple RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutral...

Page 37: ...even partial of this manual is strictly forbidden 37 DM 2 5 TED2T WH M White Neutral BK M Black GY M Grey YE M Yellow BU M Blue GN M Green BN M Brown RD Red BN VC H Brown valve actuator line BU VC H B...

Page 38: ...Ductimax Technical manual 38 DM 6 TED2T WH M White Neutral BK M Black GY M Grey BU M Blue RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutral...

Page 39: ...pying even partial of this manual is strictly forbidden 39 DM 1 TED4T WH M White Neutral BK M Black BU M Blue GY M Grey BN M Brown VT M Purple RD Red BN VC H Brown valve actuator line BU VC H Blue val...

Page 40: ...uctimax Technical manual 40 DM 2 5 TED4T WH M White Neutral BK M Black GY M Grey YE M Yellow BU M Blue GN M Green BN M Brown RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutra...

Page 41: ...opying even partial of this manual is strictly forbidden 41 DM 6 TED4T WH M White Neutral BK M Black GY M Grey BU M Blue RD Red BN VC H Brown valve actuator line BU VC H Blue valve actuator neutral FL...

Page 42: ...ue pump power supply neutral BK FLOAT Black float switch alarm signal GY FLOAT Grey COM alarm SUM WIN No voltage contact for remote ECONOMY VC 0 10V Water valve cold for 4 pipe hydronic indoor unit mo...

Page 43: ...RT BASE having the following main features Room air temperature reading and adjustment Water temperature reading water probe as an optional Manual and automatic adjustment of fan speed Manualandautoma...

Page 44: ...or 2 ON OFF valves Control of additional heating element on board timer function to detect the actual ambient air temperature Reading of air ambient temperature set point fan speed and mode selection...

Page 45: ...ng to access the unit fitted behind the ceiling panels or in a service room CM Delivery plenum boxes DeliveryPlenumboxesingalvanisedsheetmetalcompletewithcircularcollars 200mm fortheconnectionbymeanso...

Page 46: ...adjusting valves the hydraulic unions and the holdfasts during the cooling operating mode The trays are made of galvanized metal sheet with condensate discharge pipe 17 mm setup for being connected t...

Page 47: ...from the power supply by setting the main switch on 0 OFF To clean the air filter proceed as follows 1 Access the unit via the inspection panel and take out the air filter as shown in Air filter 2 If...

Page 48: ...Ductimax Technical manual 48 MAFO standard air intake Air intake MAF90 MAFO90...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...via Romagnoli 12 a 40010 Bentivoglio BO Italy Ph 39 051 8908111 Fax 039 051 8908122 www galletti com...

Reviews: