UT66002214-05
All copying, even partial, of this manual is strictly forbidden
9
5 RATED TECHNICAL DATA
» 2 pipes
DUCTIMAX
13
14
23
24
Speed
min
med
max
min
med
max
min
med
max
min
med
max
Declared speed
2,5,7
2,5,7
1,5,7
1,5,7
Rated air flow
(E)
m³/h
109
246
276
109
246
276
171
275
341
171
275
341
Available static pressure
(E)
Pa
10
50
63
10
50
63
19
50
77
19
50
77
Power input
(E)
W
24
57
82
24
57
82
34
69
106
34
69
106
Maximum current absorption
A
0,40
0,40
0,56
0,56
Total cooling capacity
(1)(E)
kW
0,92
1,72
1,90
0,95
1,91
2,11
1,27
1,90
2,27
1,36
2,11
2,53
Sensible cooling capacity
(1)(E)
kW
0,61
1,21
1,34
0,63
1,30
1,43
0,89
1,34
1,59
0,93
1,44
1,72
FCEER class
(E)
D
Water flow
(2)
l/h
160
306
340
167
337
375
222
339
408
239
374
453
Water pressure drop
(2)(E)
kPa
2
5
6
2
7
8
3
6
8
4
8
12
Heating capacity
(3)(E)
kW
0,88
1,81
1,99
0,91
1,98
2,21
1,33
1,98
2,35
1,40
2,20
2,68
FCCOP class
(E)
D
Water flow
(3)
l/h
153
315
346
158
345
384
231
345
408
244
382
466
Water pressure drop
(3)(E)
kPa
1
4
5
2
6
7
2
5
7
3
7
10
Standard coil - number of rows
3
4
3
4
Total sound power level
(4)
dB(A)
28
49
52
28
49
52
39
50
54
39
50
54
Inlet + radiated sound power level
(4)(E)
dB(A)
26
47
50
26
47
50
37
46
52
37
46
52
Outlet sound power level
(4)(E)
dB(A)
25
46
49
25
46
49
36
45
51
36
45
51
Water content - standard coil
dm³
1,20
1,60
1,20
1,60
Power supply cable type
N07V-K
Cross-section area of power cables
(5)
mm²
1,00
1,00
1,00
1,00
Safety fuse F
A
1
1
1
1
Fuses type
gG
DUCTIMAX
33
34
43
44
Speed
min
med
max
min
med
max
min
med
max
min
med
max
Declared speed
1,6,7
1,6,7
1,4,7
1,4,7
Rated air flow
(E)
m³/h
195
360
402
195
360
402
305
532
652
305
532
652
Available static pressure
(E)
Pa
19
50
63
19
50
63
17
50
75
17
50
75
Power input
(E)
W
34
85
106
34
85
106
76
143
192
76
143
192
Maximum current absorption
A
0,56
0,56
1,10
1,10
Total cooling capacity
(1)(E)
kW
1,44
2,28
2,51
1,57
2,69
2,96
1,92
3,17
3,68
2,29
3,78
4,45
Sensible cooling capacity
(1)(E)
kW
1,01
1,69
1,86
1,07
1,86
2,03
1,42
2,39
2,81
1,57
2,61
3,08
FCEER class
(E)
D
D
E
D
Water flow
(2)
l/h
252
406
449
274
476
527
343
568
664
407
673
798
Water pressure drop
(2)(E)
kPa
2
5
5
3
7
9
3
8
11
6
14
18
Heating capacity
(3)(E)
kW
1,57
2,70
2,96
1,59
2,80
3,10
2,35
3,71
4,31
2,41
3,95
4,68
FCCOP class
(E)
D
Water flow
(3)
l/h
272
470
515
276
488
538
408
644
749
419
687
814
Water pressure drop
(3)(E)
kPa
2
5
6
2
6
8
4
9
11
5
12
16
Standard coil - number of rows
3
4
3
4
Total sound power level
(4)
dB(A)
39
50
54
39
50
54
38
52
58
38
52
58
Inlet + radiated sound power level
(4)(E)
dB(A)
37
48
52
37
48
52
36
50
56
36
50
56
Outlet sound power level
(4)(E)
dB(A)
36
47
51
36
47
51
35
49
55
35
49
55
Water content - standard coil
dm³
1,60
2,20
1,60
2,20
Power supply cable type
N07V-K
Cross-section area of power cables
(5)
mm²
1,00
1,00
1,50
1,50
Safety fuse F
A
1
1
2
2
Fuses type
gG
Summary of Contents for Ductimax