DMC-40x0 Command Reference
EP • 99
EP
FUNCTION
:
Cam table intervals and starting point
DESCRIPTION:
The EP command defines the ECAM table intervals and offset. The offset is the master position
of the first ECAM table entry. The interval is the difference of the master position between 2
consecutive table entries. This command effectively defines the size of the ECAM table. The
parameter m is the interval and n is the starting point. Up to 257 points may be specified.
ARGUMENTS
: EP m,n
where
m is a positive integer in the range between 1 and 32,767
m = ? Returns the value of the interval, m.
n is an integer between -2,147,483,648 and 2,147,483,647. n is the offset.
USAGE: DEFAULTS:
While Moving
Yes
Default Value
In a Program
Yes
Default Format
Command Line
Yes
Controller Usage
ALL CONTROLLERS
OPERAND USAGE:
_EP contains the value of the interval m.
RELATED COMMANDS:
Choose ECAM master
Enable ECAM
Set ECAM table index
Engage ECAM
Specify ECAM cycle
Disengage ECAM
ECAM table
EXAMPLES:
EP 20,100
Sets the cam master points to 100,120,140 . . .
D = _EP
Set the variable D equal to the ECAM internal valve