P a g e
|
18
Figure 8 Bonding GAF Solar Module Assembly to Copper Wire
The adjustable feet and MLPE bracket are bonded to the GAF frame with the provided hex grounding
screw (10-32x3/8”, serrated washer, thread cutting type F) as shown in Figure 9 below.
The two parts of the Adjustable Foot Assembly are bonded together via the provided hardware as shown
in
Figure 10
below.
The Top Flashing and Top Corner Flashing are bonded together using UL-approved DynoRaxx®
DynoBond™ Grounding Jumpers as shown in
Figure 7
above. A single 38" DynoBond™ is used between
two flashing pieces. The 76" DynoBond™ is used in one location to provide bonding between the flashing
pieces and the bare copper system ground wire.
Figure 11
below shows how the DynoBond® clip attaches
to the flashing piece.
Figure 12
shows the connection between the 76” DynoBond® jumper and bare
copper wire at one of the MLPE WEEB® Ground Lugs.
Grounding Screw
External Tooth
Washer
Bare Solid Copper
Grounding Wire
WEEB
®
Grounding
Assembly
Figure 9 Feet and bracket bonding screw
Figure 10 Adjustable Foot Bonding Hardware
Internal Tooth
Washer
Serrated Nut