3.5.2.3
Counters
Any of the internal inputs of the RTU-810 has a double function and acts in parallel as
an event counter or a time counter with a 16 bit register.
Configured as an event counter, each time the input changes from off to on, an event is
counted. The maximum frequency is 10 Hz. This can be used as a pulse counter.
Configured as a time counter, the counting register will be increased by 1 in every
second the input is active. Resolution is 100ms.
The 16 bit register will turn over from 65535 to 0, this must be taken into account in the
SCADA when calculating the events or seconds from the delta between two pollings.
This page configures whether each input acts as an
even counter or as a time counter. Default setting is
port A as event counters, port B as time counters.