Due to the fact that this recalculation happens any time "Apply" is pressed, it is
recommended to configure the I/O transfers for slave 1, then press "Apply" to update
the information for the slaves 2-4.
Then slave 2 can be configured, pressing "Apply" after the configuration to update the
ranges for the slaves 3 and 4 … and so on.
If all slaves are configured at once, it'll be possible to enter more I/O in total as are
available on the master RTU-810. In this case, after pressing "Apply", an error message
will indicate this fact on the page:
The communication to the slaves will not be established unless these errors are cleared!
3.2.3.3
Error messages
If there are any major configuration issues which stops the master RTU mode from
working, these are listed in the "Error messages" field:
Note: Any events are logged into the Event Logger, also single station events which
do not affect the communication of the RTU-810 master to the other stations (like
communication losses etc.